1

Ťažká

What additional protective equipment will you use when brazing systems containing HC refrigerants?


Latex gloves
Ear defenders
A high-visibility vest
A flammable gas detector

2

Ťažká

Why can’t a sealed high-pressure switch be replaced with a standard mechanical one in a system containing a flammable refrigerant?


The pressure switch setting will not be correct
It is a potential source of ignition
There is a risk of refrigerant leakage
Dust and moisture may enter

3

Ťažká

What is the minimum (recommended) distance from a work area with HC refrigerants within which there must be no sources of ignition?


3 m
2 m
0.5 m
1 m

4

Ťažká

What is the maximum safe R32 fill of a recovery cylinder approved for flammable gas that holds 20 kg of R410A (the liquid density of R32 is about 8-10% lower)?


33 kg
18 kg
20 kg
9 kg

5

Ťažká

What is the maximum charge of an A3 refrigerant for a hermetic display cabinet with an integral condenser located in the ground-floor sales area of a supermarket?


0,494 kg
2.5 kg
10 kg
1.0 kg

6

Ťažká

How can a vacuum pump be used safely to evacuate a system containing a flammable refrigerant?


Place the pump directly on the floor, as low as possible
Such systems need not be evacuated before charging
Ignition-source-free pump, good ventilation, exhaust to a safe place
Position the pump at least 3 m above floor level

7

Ťažká

What safety measure must you carry in your vehicle when transporting flammable refrigerant cylinders?


A fire extinguisher
Tinted safety goggles
Thick gloves
A fire blanket

8

Ťažká

How would you prepare a 10 kg R32 water chiller located outdoors for debrazing its joints?


Recover the R32 to a vacuum and start desoldering immediately
Recover the R32 to a vacuum, then fill the system with nitrogen to a slight positive pressure (approx. 0.1 bar g)
Vent the R32 outdoors, then fill and vent the system with nitrogen three times
Vent the R32 outdoors and purge the system

9

Ťažká

Which of the following leak detection methods should NOT be used to locate an HC refrigerant leak?


Soapy water solution
Electronic HFC leak detector
Electronic leak detector for flammable refrigerants
Leak detection foam

10

Ťažká

What is the most important difference between a flammable refrigerant recovery unit and a standard one?


A flammable refrigerant recovery unit has no ignition sources
Different connection sizes
A different colour for the station
Different low-pressure switch setting

11

Ťažká

Which of the following is a source of ignition?


A sealed NTC temperature sensor
A contactor (sparking contacts)
An Ex-certified fan motor
An 'n'-type (non-sparking) thermostat

12

Ťažká

What particularly hazardous substance is formed when R32 burns?


Phosgene
Hydrogen fluoride (HF)
Hydrogen chloride (HCl)
Sulphur dioxide (SO₂)

13

Ťažká

What type of refrigerant is R1234ze(E)?


HC (hydrocarbon)
CFC (chlorofluorocarbon)
HCFC (hydrochlorofluorocarbon)
HFO (hydrofluoroolefin)

14

Ťažká

What hazards does a safety group A3 refrigerant pose?


Lower toxicity, moderate flammability
Higher toxicity, moderate flammability
Higher toxicity, higher flammability
Lower toxicity, higher flammability

15

Ťažká

According to EN 378, what is the maximum R290 charge in a cold room measuring 5 m × 3 m × 2.5 m (LFL of R290 = 0.038 kg/m³, access category a, location class I, no additional measures))?


1.0 kg
4.93 kg
0.285 kg
1.5 kg

16

Ťažká

What is the approximate ratio of the volumetric cooling capacity of R32 to that of R410A (same compressor and conditions)?


approx. 0.6
approx. 1.3
approx. 1.05–1.1
approx. 0.75

17

Ťažká

Why are Ex-certified evaporator fan motors used in some systems with flammable refrigerants?


Because they are more energy-efficient
To avoid a source of ignition in the event of a flammable refrigerant leak
Because they must be kept running continuously to disperse the leaking refrigerant
Because they are more reliable

18

Ťažká

Why is the density difference between HC and HFC refrigerants important?


An HC charge in kg is roughly half that of an HFC
Because HCs operate at much higher pressures
Because HCs must be charged much more slowly than HFCs
Because it determines the system's energy efficiency

19

Ťažká

What is the GWP of R290 according to Annex VI to Regulation (EU) 2024/573?


7
675
150
0.02

20

Ťažká

Which of the following is NOT a source of ignition?


An unsealed mechanical pressure switch
An Ex-certified fan motor
An electrical switch
A light switch

21

Ťažká

What is R290?


Isobutane
Butane
Propane
Propene (Propylene)

22

Ťažká

What is the maximum A2L charge for a hermetic display cabinet with integral condenser in the ground-floor sales area of a supermarket?


150 g
1.2 kg
1.5 kg
2.5 kg

23

Ťažká

Why can’t a standard relay be fitted when retrofitting a compressor’s electrical system for flammable refrigerants?


A relay is never required for compressors using flammable refrigerants
The method of starting the compressor motor differs from that used with HFCs
Current consumption differs for compressors using flammable refrigerants compared to those using HFCs
It could be a source of ignition

24

Ťažká

What is the minimum (recommended) distance from a work area with HC refrigerants within which there must be no ignition sources?


1 m
10 m
5 m
3 m

25

Ťažká

A recovery cylinder holds 10 kg of R404A (filling ratio 0.82 kg/l). What is the maximum R290 charge for this cylinder (propane filling ratio 0.43 kg/l per ADR P200)?


approx. 5.2 kg
20 kg
approx. 17 kg
approx. 8 kg

26

Ťažká

How can a vacuum pump be used safely to evacuate a system containing R290?


Place the pump directly on the floor, as low as possible
Position the pump at least 3 m above floor level
R290 systems need not be evacuated before charging
Ignition-source-free pump, good ventilation, exhaust to a safe place

27

Ťažká

Under ADR, what equipment must you carry in your vehicle when transporting flammable refrigerant cylinders (under the 1.1.3.6 exemption)?


A fire extinguisher (at least 2 kg dry powder)
Tinted safety goggles
Thick gloves
A fire blanket

28

Ťažká

How do you make sure it is safe to light the torch for desoldering joints in a system from which a flammable refrigerant has been removed?


Working outdoors is sufficient
Such joints must never be desoldered; they must be cut with a pipe cutter
Purge the system with compressed air
Ensure good ventilation and check the work area with a flammable gas detector

29

Ťažká

How would you prepare a system containing 100 g of R1270 for debrazing, if local regulations allow controlled venting of small HC quantities?


Vent the R1270 outdoors and start brazing immediately
Recover the R1270 to a vacuum and start brazing immediately without a nitrogen purge
Vent the R1270 to a safe outdoor location, then purge with OFN three times (pressurise and vent), and braze with OFN flowing
Vent the R1270 into the room and open a window

30

Ťažká

Which method should NOT be used to locate an R290 leak?


An electronic leak detector designed for HFCs
An electronic detector for flammable refrigerants
Leak detection foam
Fluorescent dye and UV lamp (if approved by the manufacturer)

31

Ťažká

Why can’t recovery stations designed for HFCs be used with R600a?


The low-pressure switch setting will not be suitable for R600a due to its lower operating pressure
The recovery unit cannot withstand the working pressure of R600a
The oil in the recovery unit is not soluble in R600a
They contain ignition sources

32

Ťažká

According to EN 378, what is the maximum R1234ze(E) charge in a cold room measuring 5 m × 3 m × 2.5 m (LFL = 0.303 kg/m³, access category a, location class I, no additional measures)?


227 kg
618 kg
6.18 kg
2.27 kg

33

Ťažká

What type of refrigerant is R32?


Hydrofluoroolefin
Hydrocarbon
Hydrofluorocarbon
Carbon dioxide

34

Ťažká

What hazards do A2L refrigerants pose?


Higher toxicity, lower flammability
Lower toxicity, lower flammability (burning velocity ≤ 10 cm/s)
Higher toxicity, higher flammability
Lower toxicity, higher flammability

35

Ťažká

What hazard is associated with the combustion of HFO or HFC refrigerants?


Phosgene is formed
Nitrous oxide is formed
Ozone is formed
Hydrogen fluoride (HF) is formed

36

Ťažká

Approximately what compressor displacement is required for R600a compared with R134a for the same cooling capacity?


About twice as large
The same
About seven times as large
About half

37

Ťažká

What is the GWP value for R32 according to Regulation (EU) 2024/573?


0
7
3
675

38

Ťažká

Why is charge accuracy more important in critically charged R290 systems than in HFC systems?


The charge mass is much smaller than in an HFC system, because the liquid density of R290 is much lower
Because R290 is only used in systems below 150 g
Because of lower operating pressures
Because such systems never have liquid receivers

39

Ťažká

Why does the condenser fan run continuously in some systems using R1270?


To dilute the refrigerant in the event of a leak
To prevent the build-up of contaminants in the condenser
To ensure that the discharge pressure never becomes excessive
To reduce energy consumption

40

Ťažká

What is the role of a suction liquid separator (also in systems with flammable or toxic refrigerants)?


It separates liquid from oil
It prevents liquid refrigerant from entering the compressor
It heats the refrigerant before the evaporator
It is used only to measure moisture

41

Ťažká

What is the function of an oil separator in systems using flammable or toxic refrigerants?


They are used solely to measure the moisture content of the refrigerant
It prevents liquid from entering the compressor
Heats the refrigerant before it enters the evaporator
Separates oil from the refrigerant and facilitates the return of oil to the compressor

42

Ťažká

Why do liquid and oil separators in CO₂ systems require particular attention?


Because of very high pressures – adequate PS and protection devices are required
Because CO₂ needs no lubrication, so oil separators are unnecessary
Because CO₂ is flammable and separators must not be used
Because sight glasses and level indicators must not be used in CO₂ systems

43

Ťažká

What is the critical pressure of CO₂ (R744)?


Approx. 120 bar
Approx. 31 bar
Approx. 10 bar
Approx. 74 bar (abs)

44

Ťažká

What characterises the transcritical process in CO₂ systems?


It occurs only at low temperatures
Conventional condensation occurs
It is irrelevant to system operation
Heat rejection takes place above the critical point – the refrigerant does not condense in the conventional way (gas cooler instead of condenser)

45

Ťažká

What characterises the subcritical CO₂ process?


Operation above the critical point
The conventional condensation process below the critical point
The absence of evaporation
The absence of condensation

46

Ťažká

When can dry ice (solid CO₂) form?


During normal operation of the system
When the pressure drops suddenly below the triple point (approx. 5.2 bar abs, −56.6 °C), e.g. when venting liquid CO₂ or charging liquid into an evacuated system
At high pressure
At high temperature

47

Ťažká

What risks are associated with dry ice forming in a CO₂ system?


Improved efficiency
Blocked pipes and valves and system damage (and a sharp pressure rise when it thaws)
No risk
Pressure reduction

48

Ťažká

How does CO₂ saturation pressure change as temperature increases?


It remains the same
It decreases
It first decreases, then increases
It increases rapidly

49

Ťažká

What happens to CO₂ above the critical point?


It turns into a liquid
It ceases to conduct heat
It transitions to a supercritical state (no distinction between liquid and gas)
It turns into a solid

50

Ťažká

What is the main difference between a dry-expansion and a flooded evaporator?


A dry-expansion evaporator is filled with liquid, a flooded one with vapour
A dry-expansion evaporator always has a lower pressure than a flooded one
In a dry-expansion evaporator the refrigerant completely evaporates and is superheated in the evaporator; in a flooded one part of the refrigerant remains liquid (incomplete evaporation, no superheat)
A dry-expansion evaporator needs no expansion valve, a flooded one does

51

Ťažká

What is the typical pressure in the evaporator of an R717 deep-freeze system (below −40 °C)?


Positive pressure of 10–20 bar
Positive pressure of 5–10 bar
Below atmospheric (approx. 0.7 bar abs at −40 °C)
Atmospheric pressure, approx. 1 bar abs

52

Ťažká

Why are PFAS formed by the decomposition of certain F-gases (e.g. TFA from HFOs) problematic?


They are very persistent, accumulate in the environment (e.g. water) and may be toxic
They are readily biodegradable
They cause rapid cooling of the atmosphere
They are climate- and environment-neutral

53

Ťažká

How is oil managed in R717 systems?


Oil has no effect on system operation
Oil requires no monitoring
Oil can be mixed with any refrigerant
Oil collecting at the lowest points of vessels is regularly checked and drained, because it impairs heat transfer

54

Ťažká

What should be done with contaminated R717?


Release it into the atmosphere
Dilute it with water and reuse it
Continue to use it without restriction
Purify it or send it for disposal in accordance with regulations

55

Ťažká

What should be done if an NH₃ leak is detected?


Evacuate people immediately and raise the alarm; stop the leak only if it is safe to do so and with suitable PPE (respiratory protection)
Carry on working wearing a dust mask
Carry on working with the room door open
Increase the pressure in the system

56

Ťažká

What role do scrubbers play in NH₃ systems?


Neutralise ammonia through absorption in a liquid (e.g. water)
They increase the pressure in the system
They are used to measure temperature
They store the refrigerant

57

Ťažká

How should the system be prepared before filling with R717?


The pressure must be increased above the standard level
There is no need to check it
Check for leaks, remove air and moisture, and create a vacuum
Simply start it up

58

Ťažká

What are the transport requirements for R717?


It can be carried in open containers
It must be carried in suitable, labelled packagings in accordance with ADR (UN 1005, class 2, code 2TC)
It can be carried without labelling
Transport is not regulated

59

Ťažká

What is the main characteristic of R744 (CO₂) refrigeration systems?


Very high operating pressures
Low operating pressures
No need for control
Low energy efficiency under all conditions

60

Ťažká

What are the requirements for piping materials in CO₂ systems?


They must withstand high pressures (e.g. stainless steel, high-strength copper-alloy tubes such as K65)
Any material may be used
It doesn't matter
Only plastics

61

Ťažká

How does a booster system work in CO₂ installations?


Low-temperature (LT) compressors discharge into the suction of medium-temperature (MT) compressors – two-stage compression in a single circuit
It reduces the refrigerant quantity
It reduces evaporator pressure
It is used to store refrigerant

62

Ťažká

Why is pressure optimisation in CO₂ systems crucial?


It reduces the ambient temperature
It doesn’t matter
It reduces the amount of refrigerant
It enables the system to achieve maximum energy efficiency in transcritical mode

63

Ťažká

What role does parallel compression play in CO₂ systems?


It compresses flash gas from the intermediate receiver directly to high pressure, improving efficiency
It increases energy consumption
It has no significance
It lowers the ambient temperature

64

Ťažká

How does an ejector work in a CO₂ system?


It uses the energy of the higher-pressure refrigerant to raise the pressure of the refrigerant from the lower stage, which improves efficiency
Stores the refrigerant
It lowers the evaporator temperature
It increases the amount of refrigerant

65

Ťažká

What is the function of liquid ejectors in CO₂ systems?


They reduce atmospheric pressure
They return liquid from the separator and allow partially flooded evaporator operation (better evaporator feed)
They increase the amount of oil
They raise the refrigerant temperature

66

Ťažká

What are the characteristics of partially flooded systems in CO₂ systems?


The absence of liquid in the evaporator
Lack of regulation
The presence of liquid in the evaporator, which improves heat transfer and efficiency
Low operating pressure

67

Ťažká

What is the main risk associated with standstill pressure in CO₂ systems?


A pressure rise as the refrigerant warms up during standstill (possibly exceeding PS and lifting the relief valves)
A decrease in refrigerant quantity
Increased efficiency
A drop in temperature

68

Ťažká

How is standstill pressure limited in CO₂ systems?


By increasing the refrigerant charge
By using an auxiliary standstill (stagnation) cooling unit, e.g. cooling the receiver, with back-up power, and by selecting an adequate PS and relief valves
By completely shutting down the system and power supply
By raising the plant-room temperature

69

Ťažká

What does standstill (stagnation) of a CO₂ system mean, and why is it important?


Improved efficiency
Normal system operation
A drop in system temperature
A state with no compressor operation or refrigerant flow – pressure rises with ambient temperature and may exceed PS

70

Ťažká

What must the label of a flammable refrigerant cylinder include?


Only the net weight
The refrigerant name, the UN number, the hazard label (e.g. 2.1 – flammable gas) and basic safety information
Only the refrigerant name
Information about the cylinder owner

71

Ťažká

Why is the absence of a 'flammable refrigerant' label on equipment a serious hazard?


It reduces system efficiency
It may lead to the wrong oil being selected
It has no significant effect on safety
It may lead to the use of tools that are ignition sources

72

Ťažká

Which set of information on the label of a flammable refrigerant cylinder is crucial from a safety perspective?


Cylinder colour and date of manufacture
Name of the substance, hazard label (ADR) / GHS pictogram (CLP), UN number
Manufacturer’s name and country of origin
Gross weight and batch number

73

Ťažká

What is the purpose of gas detectors in a room with a refrigeration system?


Monitoring pipe pressure
Controlling compressor capacity
Early leak detection and triggering of measures preventing health risks and explosive atmospheres (alarm, ventilation, shut-off)
Measuring refrigerant temperature

74

Ťažká

How often should gas detection sensors in a machinery room be checked?


Only after a leak has occurred
Once every 5 years
According to the manufacturer's instructions and regulations – at least every 12 months
Before every start-up of the unit

75

Ťažká

Where should a gas detector be located according to EN 378?


Only at the room entrance
Where the refrigerant would accumulate: low (near the floor) for refrigerants heavier than air, high (near the ceiling) for lighter ones such as NH₃
Near the control panel
Anywhere in the room

76

Ťažká

What safety checks should be carried out when installing a new refrigeration system with a flammable refrigerant?


Only that the air filter is new
The colour of pipes and hoses
Only the compressor power
The presence of health and safety signage, adequate ventilation and gas detectors

77

Ťažká

What are the requirements for emergency exits from a refrigeration machinery room?


At least two exits are required and signage is optional
Outward-opening doors and signed escape routes (number of exits per the standard)
In small machinery rooms emergency exits need not be signed
One exit with a sign stating the refrigerant type is sufficient

78

Ťažká

Which installation measure for a flammable-refrigerant system improves its energy efficiency?


A thorough tightness test and evacuation (dehydration) of the system
Charging above the nameplate quantity
Omitting the filter-drier
Restricting room ventilation

79

Ťažká

Why is it important to limit the refrigerant charge in HC systems?


It doesn't matter
It limits the possibility of reaching a flammable concentration (≥ LFL) in a leak, increasing safety
It lowers the temperature
It increases capacity

80

Ťažká

Which safety class applies to R744?


A3
B2L
A2.
A1

81

Ťažká

In a simple single-stage R744 system without an intermediate receiver (refrigerant flows from the gas cooler directly to the expansion valve), operating transcritically at 90 bar with a gas-cooler outlet temperature of 35 °C, the refrigerant upstream of the expansion valve is…


…saturated vapour at intermediate pressure
…a two-phase mixture at intermediate pressure
…a subcooled liquid
…a supercritical fluid

82

Ťažká

In R744 transcritical systems, the gas cooler outlet valve controls:


The pressure in the gas cooler
The inlet temperature to the gas cooler
The gas cooler fans
The outlet temperature of the gas cooler

83

Ťažká

Which statement best describes the behaviour of R717 and mineral compressor oil?


R717 mixes very well with the oil, which easily returns to the compressor
R717 does not mix with the oil; the oil, being heavier than liquid NH₃, collects beneath it at the lowest points (mainly on the low-pressure side)
An oil return line cannot be used in R717 systems because the oil is too hot
R717 does not mix with the oil; the oil collects on the high-pressure side above the R717

84

Ťažká

What is the main reason for using K65 copper tubing in some R744 systems?


They can withstand higher pressures
They have good low-temperature performance
They come in a wider range of diameters
They bend easily

85

Ťažká

Which statement about installing Schrader valves is correct?


When brazing the valve body, the core must be removed, then refitted and tightened to the correct torque
All Schrader cores are suitable for all refrigerants
Hydrocarbons leak through Schrader valves
Schrader valves must not be used in R744 systems

86

Ťažká

Which refrigerant can be detected with phenolphthalein paper?


R1270
R744
R1234ze(E)
R717

87

Ťažká

How does an undercharge affect the high-pressure side (without discharge pressure control)?


Discharge (condensing) pressure and subcooling will both be lower
Discharge pressure higher, subcooling higher
Discharge pressure lower, subcooling higher
Discharge pressure higher, subcooling lower

88

Ťažká

What is the benefit of adding helium as a tracer gas to nitrogen in a pressure test?


It reacts with refrigerant residues, producing a visible colour change
It has a higher pressure than pure nitrogen in the same cylinder
It has a distinctive odour that helps locate the leak
Its small atoms pass easily through leaks and are detected

89

Ťažká

Why should an evacuated R744 system initially be charged with refrigerant in the vapour phase?


To prevent the drain valve on the receiver from opening
To prevent dry ice forming (until approx. 5.2 bar abs is exceeded)
To charge R744 more slowly and measure it more accurately
To avoid damaging the compressor with liquid CO₂

90

Ťažká

If moisture remains in an R744 system because it was not properly evacuated (dehydrated), what is the likely consequence?


Formation of hydrogen fluoride and hydrofluoric acid
Formation of carbonic acid, which damages the system
Reduced cooling capacity
Excessive discharge pressure

91

Ťažká

Which system may require manual oil recovery?


Supercritical ‘booster’ system using R744
R744 cascade system
Secondary system using R744
An R717 system

92

Ťažká

The pressure of R744 at a saturation temperature of 20 °C is approx.


90 bar g
56 bar g
25 bar g
14 bar g

93

Ťažká

Which refrigerant is lighter than air?


R1270
R744
R1234ze(E)
R717

94

Ťažká

What hazards are associated with a safety group A3 refrigerant?


Higher flammability, lower toxicity
Lower toxicity, no flame propagation
Higher toxicity, no flame propagation
Lower flammability, lower toxicity

95

Ťažká

What is the GWP of R32 (per AR4, as used in Regulation (EU) 2024/573)?


675
6
3922
0

96

Ťažká

What factors are taken into account when determining the maximum charge for comfort air-conditioning/heating applications?


Practical limit, room volume
Lower flammability limit, height of the indoor unit, floor area
Lower flammability limit, room volume
Practical limit, height of the indoor unit, floor area

97

Ťažká

What compressor displacement is required for R1270 compared with an R404A compressor in the medium-temperature range (cold room)?


About half
About 1.5 times larger
About 6 times larger
Similar

98

Ťažká

At an ambient temperature of 25 °C, the standstill pressure in the low-pressure stage of an R744 cascade (without standstill cooling) will typically be…


…higher than the maximum allowable pressure (PS) of the low-pressure stage
…approx. 27.5 bar g
…the same as the high-pressure switch setting
…the same as the relief valve set pressure

99

Ťažká

What is the correct definition of critical temperature?


The temperature at which the vapour pressure of a liquid is equal to the ambient pressure surrounding the liquid
The temperature at which a substance changes from a gaseous to a solid state
The temperature above which there are no distinct liquid and gaseous phases
The temperature at which, for certain substances, electrical resistance is zero

100

Ťažká

In the gas cooler of a transcritical system, the supercritical working fluid…


…rejects heat at constant temperature and pressure
…rejects heat during a phase change
…rejects heat as its temperature falls
…rejects heat as its pressure falls

101

Ťažká

R717 is highly corrosive to:


titanium
aluminium
stainless steel
copper (and its alloys)

102

Ťažká

What can be the effect of a relief valve lifting repeatedly?


The valve no longer opens
The valve stays fully open permanently
The valve may not reseat tightly and its set (opening) pressure may decrease
The set pressure increases

103

Ťažká

What is the relationship between the pressure (p) and temperature (T) of nitrogen at the start (1) and end (2) of a tightness test (p absolute, T in kelvin)?


p₂ = T₂/(p₁ × T₁)
p₂ = (p₁ × T₂)/T₁
p₂ = (p₁ × T₁)/T₂
p₂ = T₁/(p₁ × T₂)

104

Ťažká

What is the recommended pre-alarm level for fixed leak detection systems for R717?


500 ppm
5,000 ppm
500,000 ppm
50,000 ppm

105

Ťažká

Why are compressors with a separate motor (open type) mostly used in R717 systems?


Because they are cheaper
To increase the refrigerant charge
Because NH₃ attacks copper motor windings, so hermetic compressors with conventional windings are not used
To lower the condensing pressure

106

Ťažká

Which type of compressor is most commonly used in large ammonia systems?


Rotary vane compressor
A reciprocating or screw compressor
Hermetic scroll
Diaphragm compressor

107

Ťažká

How is the capacity of a piston compressor regulated in NH₃ systems?


By reducing the refrigerant charge
Solely by adjusting the oil volume
By increasing the condensing pressure
By unloading the cylinders or changing the rotational speed

108

Ťažká

How is the capacity of a screw compressor most commonly controlled?


By adjusting the oil level
By using a slide valve
By changing the type of oil
By closing the suction valve

109

Ťažká

When is two-stage compression used in NH₃ systems?


At small temperature differences
Only with water-cooled condensers
At low evaporating temperatures (pressures) and high pressure ratios
Only in small systems

110

Ťažká

What is the advantage of two-stage compression over single-stage compression?


Lower efficiency
Higher efficiency and lower discharge temperature
Higher energy consumption
No need for a separator

111

Ťažká

How does an evaporative condenser used in NH₃ systems work?


It transfers heat only to the air
Operates without a fan
It utilises the evaporation of water to increase cooling efficiency
It does not require a water supply

112

Ťažká

What is the function of the liquid separator in an NH₃ system?


It separates oil from the refrigerant
Regulates the condensing pressure
It prevents liquid from entering the compressor
Increases the discharge temperature

113

Ťažká

What is the purpose of monitoring the liquid level in the separator?


To maintain the correct refrigerant level and prevent the compressor from flooding
To increase the oil volume
To control the condenser fan
To reduce the condensing temperature

114

Ťažká

What is the role of the float switch in NH₃ systems?


It monitors the liquid level in the tank or separator
It regulates the condensation temperature
It controls the fan’s operation
It is used to detect leaks

115

Ťažká

What is a thermosyphon in NH₃ systems?


A type of safety valve
A system with gravity-driven (natural) circulation of liquid refrigerant caused by density differences, used e.g. for screw compressor oil cooling
An oil circulation pump
A defrosting device

116

Ťažká

Why are oils that are immiscible with the refrigerant used in NH₃ systems?


To increase the amount of refrigerant
Because NH₃ does not mix with most compressor oils
Because the oil mixes only with water
To reduce the pressure

117

Ťažká

What is the main function of an oil separator in NH₃ systems?


Removing moisture from the system
To increase fan efficiency
To lower the condensation temperature
To separate the oil from the refrigerant and return the oil to the compressor

118

Ťažká

In which NH₃ system does the refrigerant evaporate completely with superheat in the evaporator, fed by an expansion valve?


An indirect system
A direct-expansion (DX) system
A pumped liquid-recirculation system
A glycol system

119

Ťažká

What is the characteristic feature of a flooded evaporator system?


No separator is used
The evaporator is filled exclusively with vapour
No level control is required
The evaporator contains a large amount of liquid, which improves heat transfer

120

Ťažká

What is the main difference between a direct and an indirect system?


In an indirect system, no compressor is used
In a direct system, there is no evaporator
In an indirect system, NH₃ flows directly into the space being cooled
In an indirect system, NH₃ cools an intermediate medium (e.g. glycol), which in turn cools the load

121

Ťažká

Which parts of a refrigeration system should be given particular attention during a leak check?


Compressor and receiver connections, because the pressure is highest there
Only condenser connections, because the refrigerant is liquid there
Only compressor connections, because they are the only parts subject to vibration
Joints, valves incl. stems, seals, parts subject to vibration, connections to safety devices

122

Ťažká

Leak checks can be carried out using various methods. Which pair is correct?


Physical and chemical methods
Direct and indirect methods
Material quality control methods and electronic methods
Methods with and without quality control of supplies

123

Ťažká

To whom can leak checks of stationary refrigeration equipment containing F-gases be entrusted?


An employee appointed by the owner of the installation
Any leak-testing specialist
A natural person holding a certificate covering leak checks (A1, A2 within its charge limit, or E)
A person who has carried out such checks before

124

Ťažká

What conditions must be met to use UV dye for leak checking?


It is sufficient that introducing dye into the circuit is technically feasible
Manufacturer approval of the method and a certificate covering breaking into the circuit
It is sufficient to have a UV lamp, dye and safety goggles
A UDT authorisation for pressure testing is required

125

Ťažká

Which leak-checking methods are considered direct methods?


1. gas detection devices (portable or fixed leak detection system), 2. UV detection fluid or dye, 3. bubble/foam solutions
Pressure-change measurement and immersion in water
Nitrogen with tracer gas and pressure measurement
Vacuum test and foam solution

126

Ťažká

What do indirect leak-checking methods involve?


Ultrasonic measurement
Leak detection with UV dye
Leak detection with an electronic detector
A visual and manual check and analysis of parameters: pressure, temperature, compressor current, liquid levels and recharge volume

127

Ťažká

What does a vacuum (decay) test involve?


The pump runs continuously to hold the required vacuum for the test
After isolating the pump, you check whether the system pressure rises
The pump is restarted every time the system pressure rises
With the pump running, you watch the vacuum gauge reading

128

Ťažká

How often should leak tests be carried out on equipment containing 1.5 kg of R404A refrigerant (5.9 tonnes of CO₂ equivalent)?


Once every six months.
At least once every 12 months.
On initial commissioning.
Only when servicing the unit.

129

Ťažká

How often should leak tests be carried out on equipment containing 7 kg of R404A refrigerant (27.45 tonnes of CO₂ equivalent)?


Once every six months.
At least once every 12 months.
On initial commissioning.
Only when servicing the unit.

130

Ťažká

Under Regulation (EU) 2024/573, a leakage detection system is mandatory when:


the equipment operates in an enclosed space
the F-gas charge of the refrigeration equipment is 500 t CO₂ eq or more
the equipment contains a flammable refrigerant in any quantity
the charge is 100 kg or more of ozone-depleting substances

131

Ťažká

Which leak-checking method may NOT be used by a holder of a Category E certificate?


Visual inspection
Checking with a foaming solution
Leak checking with a fluorescent dye introduced into the circuit
Measurement with a handheld electronic detector

132

Ťažká

Within what timeframe must a leak test be carried out on a stationary refrigeration system after a leak has been repaired, in accordance with EU Regulation 2024/573 on F-gases?


At any time.
Immediately after the repair.
At the next periodic inspection.
Between 24 hours and 1 month after the repair.

133

Ťažká

How often must refrigeration equipment containing ≥500 t CO₂ eq of F-gases be checked if (contrary to Article 6) no leakage detection system is installed?


Every month
Every 12 months
Every 3 months
Every 6 months

134

Ťažká

What is the basis of the GWP values in Regulation (EU) 2024/573?


AR4 for all substances
AR6 for all substances
For HFCs (Annex I) – mainly the IPCC Fourth Assessment Report (AR4); for HFOs and non-fluorinated substances (Annexes II and VI) – the Sixth Assessment Report (AR6)
Each Member State sets its own GWP values

135

Ťažká

An air conditioner (not hermetically sealed) contains 2.5 kg of R410A (GWP 2088). How often must it be checked for leaks?


Every 3 months
Every 6 months
At least every 12 months (5.22 t CO₂ eq)
No checks required (below 3 kg)

136

Ťažká

When is labelled hermetically sealed equipment containing HFCs (Annex I) exempt from leak checks?


When it contains less than 10 t CO₂ eq, and in residential buildings also when it contains less than 3 kg of F-gases
When it contains less than 5 t CO₂ eq
Never – hermetically sealed equipment is always checked
Always, regardless of charge

137

Ťažká

Is a chiller containing 50 kg of R1234ze(E) subject to leak checks under Regulation (EU) 2024/573?


No – the threshold is 5 t CO₂ eq and 50 kg of R1234ze is below 1 t CO₂ eq
Yes – every 12 months, because its GWP is low
Yes – at least every 6 months (every 12 months with a leakage detection system)
No – HFOs are not subject to leak checks

138

Ťažká

In 2026, may an existing refrigeration installation using R404A (GWP 3922) be topped up with virgin refrigerant?


No – only reclaimed or recycled R404A is allowed (until 1 January 2030)
Yes, if the equipment has a leakage detection system
Yes – bans apply only to new equipment
Yes – the ban applies only to equipment ≥40 t CO₂ eq

139

Ťažká

After 1 January 2026, may an R410A (GWP 2088) air conditioner be serviced using virgin R410A?


Only with reclaimed refrigerant
No – the ban covers all HFCs
Yes – the servicing ban for air conditioners and heat pumps covers F-gases with GWP ≥ 2500
No – the ban covers all refrigerants with GWP ≥ 750

140

Ťažká

Since 1 January 2025, may a new single-split air conditioner containing 1.5 kg of R410A be placed on the market?


Yes – the ban applies from 2029
No – single splits <3 kg with F-gases of GWP ≥ 750 are banned
Yes – the ban applies only to units >12 kW
Yes, if the unit is hermetically sealed

141

Ťažká

From when is it prohibited to place on the market split air-to-air systems up to 12 kW containing F-gases with GWP ≥150 (unless required for safety)?


From 1 January 2027
From 1 January 2029
From 1 January 2025
From 1 January 2035

142

Ťažká

Which persistent atmospheric degradation product of R1234yf is classed as a PFAS?


Trifluoroacetic acid (TFA)
Carbon dioxide
Ozone
Carbonic acid

143

Ťažká

What is the maximum R290 charge per circuit of a commercial refrigerating appliance (e.g. a cabinet) according to EN IEC 60335-2-89:2022?


1.2 kg
1.5 kg
150 g
13 × LFL ≈ 494 g

144

Ťažká

Calculate the maximum R32 charge (LFL = 0.307 kg/m³) for a wall-mounted air conditioner (h₀ = 1.8 m) in a 20 m² room using m_max = 2.5 × LFL^1.25 × h₀ × A^0.5.


approx. 13.8 kg
approx. 4.6 kg
approx. 1.5 kg
approx. 0.46 kg

145

Ťažká

What is the maximum quantity of R290 (class 2, group F) that may be carried per transport unit under the ADR 1.1.3.6 exemption?


1000 kg
Unlimited
333 kg
20 kg

146

Ťažká

What is the charge limit m₃ = 130 m³ × LFL for R290 (LFL = 0.038 kg/m³) according to IEC 60335-2-40?


approx. 0.15 kg
approx. 0.99 kg
approx. 13 kg
approx. 4.94 kg

147

Ťažká

Why does the efficiency of transcritical CO₂ systems fall in warm climates, and how is this mitigated?


CO₂ freezes in the gas cooler – heaters are used
Gas cooler pressure drops – extra charge is added
Efficiency does not depend on climate
At high ambient temperatures the system operates transcritically with large throttling losses – parallel compression and ejectors are used, among others