F-Gas English Low GWP

All questions
HFC | Flammable | CO₂ | NH₃
Easy questions | Medium questions | Difficult questions

1

Difficult

What additional protective equipment will you use when soldering systems containing HC refrigerants?


Flammable gas detector
Fire blanket
Tinted safety goggles
High-visibility jacket

2

Difficult

Why can’t a sealed high-pressure switch be replaced with a standard mechanical one in a system containing a flammable refrigerant?


The pressure switch setting will not be correct
There is a risk of refrigerant leakage
Dust and moisture may enter
It is a potential source of ignition

3

Difficult

What is the minimum distance from the work area where HC refrigerants are used at which there must be no sources of ignition?


0.5 m
3 m
1 m
2 m

4

Difficult

What is the maximum safe charge for a recovery cylinder with R32 refrigerant, if it can be charged with 20 kg of R410A?


33 kg
20 kg
9 kg
18 kg

5

Difficult

According to EN 378, what is the maximum charge of an A3 refrigerant for a display unit (hermetic, with an internal condenser) located in the ground-floor retail area of a supermarket?


10 kg
2.5 kg
1.0 kg
1.5 kg

6

Difficult

How can a vacuum pump be used safely to evacuate a system containing a flammable refrigerant?


Fit a long hose to the pump outlet to remove HC away from the system
Use an ATEX-certified vacuum pump in a well-ventilated area
Position the vacuum pump 3 metres above floor level
There is no need to evacuate such systems

7

Difficult

What protective equipment must you have in your car when transporting flammable substances?


Tinted safety goggles
A fire extinguisher
Fire blanket
Thick gloves

8

Difficult

How would you remove the refrigerant from a 10kg R32 water chiller, located outdoors, before unsoldering the connections?


Recover the R32 until a vacuum is achieved, then charge the system with nitrogen to a relative pressure of 0.1 bar g
Vent the R32 to the outside and drain the system
Recover the R32 until a vacuum is achieved
Vent the R32 to the outside; charge the system with nitrogen until an overpressure is achieved, vent and drain the system twice, charge the system with nitrogen a third time and vent

9

Difficult

Which of the following leak detection methods cannot be used to locate an HC refrigerant leak?


Electronic leak detector for flammable refrigerants
Electronic HFC leak detector
Soapy water solution
Leak detection foam

10

Difficult

What is the most important difference between a flammable refrigerant recovery unit and a standard one?


Different low-pressure switch setting
A flammable refrigerant recovery unit has no ignition sources
A different colour for the station
Different connection sizes

11

Difficult

Which of the following is a source of ignition?


Contactor
Ex-certified evaporator fan motor
Defrost heating element
‘n’ type thermostat

12

Difficult

What substance is produced when R32 is burnt?


Hydrochloric acid
Carbon monoxide
Hydrogen fluoride
Phosgene

13

Difficult

What type of refrigerant is R1234ze?


Hydrocarbon
Chloro-fluoro-hydrocarbon
Hydrofluoroolefin
Hydrochlorofluoro-hydrocarbon

14

Difficult

What hazards does a Group A3 refrigerant pose?


High toxicity, moderate flammability
Low toxicity, highly flammable
High toxicity, high flammability
Low toxicity, moderate flammability

15

Difficult

According to EN 378, what is the maximum charge of R290 in a cold store measuring 5 m x 3 m x 2.5 m in height (the LFL for R290 is 0.038 kg/m³)?


0.285 kg
4.93 kg
1.5 kg
1.0 kg

16

Difficult

What is the cooling capacity of R32 compared to R410A?


60%
130%
75%
105%

17

Difficult

Why are Ex-certified evaporator fan motors used in some systems with flammable refrigerants?


To avoid a source of ignition in the event of a flammable refrigerant leak
Because they must be kept running continuously to disperse the leaking refrigerant
Because they are more reliable
Because they are more energy-efficient

18

Difficult

Why is the difference in density between HC and HFC refrigerants important?


Because it increases operating pressures
Because it affects the charging rate
Because it affects the charge weight
Because it affects energy efficiency

19

Difficult

What is the GWP value for R290?


675
7
3
A. 0.02

20

Difficult

Which of the following is not a source of ignition?


Open mechanical pressure switch
Light switch
An Ex-certified fan motor
Electrical switch

21

Difficult

What is R290?


Propene
Ethane
Propylene
Butane

22

Difficult

According to EN 378, what is the maximum HC refrigerant charge for a display unit (hermetic system with an internal condenser) located in the ground-floor shopping area of a supermarket?


1.0 kg
1.5 kg
150 g
2.5 kg

23

Difficult

Why can’t a standard relay be fitted when retrofitting a compressor’s electrical system for flammable refrigerants?


Current consumption differs for compressors using flammable refrigerants compared to those using HFCs
A relay is never required for compressors using flammable refrigerants
The method of starting the compressor motor differs from that used with HFCs
It could be a source of ignition

24

Difficult

What is the minimum distance from the work area where HC refrigerants are used at which there must be no sources of ignition?


1 m
3 m
10 m
5 m

25

Difficult

What is the safe charge for a recovery cylinder with R290 refrigerant, if it can be charged with 10 kg of R404A?


8 kg
20 kg
17 kg
3.6 kg

26

Difficult

How can a vacuum pump be used safely to evacuate a system containing R290?


Fit a long hose to the pump outlet to remove HC away from the system
Use an ATEX-certified vacuum pump in a well-ventilated area
Position the vacuum pump 3 metres above floor level
There is no need to evacuate systems containing R290

27

Difficult

In accordance with ADR regulations, what protective equipment must you have in your vehicle when transporting flammable refrigerants?


Thick gloves
Fire blanket
A fire extinguisher
Tinted safety goggles

28

Difficult

How do you ensure it is safe to light the torch needed to desolder joints in a system that has been evacuated of flammable refrigerant?


Purge the system with oxygen-free nitrogen
You must not desolder joints on a system containing a flammable refrigerant; they must be cut using a pipe cutter
Ensure the area is well ventilated and use a flammable gas detector to check the area
Work outdoors

29

Difficult

How would you remove the refrigerant from a system containing 100 g of R1270 so that it is ready for the joints to be desoldered?


Recover the R1270 until a vacuum is achieved, then charge the system with nitrogen to a relative pressure of 0.1 bar g
Vent the R1270 to the outside; charge the system with nitrogen until an overpressure is reached, vent and evacuate the system twice, charge the system with nitrogen a third time and vent
Recover the R1270 until a vacuum is achieved
Vent the R1270 to the outside and drain the system

30

Difficult

Which of the following leak detection methods cannot be used to locate a leak of R290 refrigerant?


Leak detection foam
Electronic HFC leak detector
Fluorescent dye and a UV lamp
Electronic leak detector for flammable refrigerants

31

Difficult

Why can’t recovery stations designed for HFCs be used with R600a?


It contains ignition sources
The low-pressure switch setting will not be suitable for R600a due to its lower operating pressure
The recovery unit cannot withstand the working pressure of R600a
The oil in the recovery unit is not soluble in R600a

32

Difficult

According to EN 378, what is the maximum charge of R1234ze in a cold store measuring 5 m x 3 m x 2.5 m in height (the LFL for R1234ze is 0.303 kg/m³)?


6.18 kg
2.27 kg
618 kg
227 kg

33

Difficult

What type of refrigerant is R32?


Hydrofluorocarbon
Hydrocarbon
Hydrofluoroolefin
Carbon dioxide

34

Difficult

What hazards do A2L refrigerants pose?


Low toxicity, high flammability
High toxicity, high flammability
Low toxicity, moderate flammability
High toxicity, moderate flammability

35

Difficult

What danger is associated with the combustion of HFO or HFC refrigerants?


Phosgene is produced
Hydrogen fluoride is produced
Nitrous oxide is produced
Citric acid is produced

36

Difficult

What is the approximate displacement volume required for a compressor running on R600a compared to one running on R134a to achieve the same cooling capacity?


Seven times
Half
The same
Twice

37

Difficult

What is the GWP value for R32?


7
3
0
675

38

Difficult

Why is the accuracy of the charge weight more important for systems critically charged with R290 compared to those using HFCs


Because these systems never have liquid receivers
Because R290 is only used in systems with a charge of less than 150g
Due to lower operating pressures
The charge mass is significantly lower than in an HFC system, as the density is much lower

39

Difficult

Why does the condenser fan run continuously in some systems using R1270?


To ensure that the discharge pressure never becomes excessive
To dilute the refrigerant in the event of a leak
To reduce energy consumption
To prevent the build-up of contaminants in the condenser

40

Difficult

What is the role of the liquid separator in systems using flammable or toxic refrigerants?


It separates the liquid from the oil
They are used solely to measure the moisture content of the refrigerant
Heats the refrigerant before it enters the evaporator
It prevents liquid from entering the compressor

41

Difficult

What is the function of an oil separator in systems using flammable or toxic refrigerants?


It prevents liquid from entering the compressor
Separates oil from the refrigerant and facilitates the return of oil to the compressor
They are used solely to measure the moisture content of the refrigerant
Heats the refrigerant before it enters the evaporator

42

Difficult

Why do CO₂ refrigeration systems require special attention when separating liquid and oil?


CO₂ operates at high pressure, which increases the risk of compressor failure and leaks
CO₂ cannot be used in systems with sight glasses
CO₂ does not require lubrication, so separators are unnecessary
CO₂ is flammable, so separators cannot be used

43

Difficult

What is the critical pressure of CO₂ (R744)?


Approximately 74 bar
Approximately 10 bar
Approximately 120 bar
Approximately 31 bar

44

Difficult

What characterises the transcritical process in CO₂ systems?


It occurs only at low temperatures
The system operates above the critical point and the refrigerant does not condense in the conventional manner
Conventional condensation occurs
It is irrelevant to the operation of the system

45

Difficult

What characterises the subcritical CO₂ process?


Operation above the critical point
The conventional condensation process below the critical point
The absence of evaporation
The absence of condensation

46

Difficult

What is the log(p)-h diagram for CO₂ used for?


To detect leaks
To measure temperature
For analysing thermodynamic processes in a refrigeration system
To regulate pressure

47

Difficult

What can be read from the log(p)-h graph?


Only the amount of refrigerant
Only the temperature
Pressure, enthalpy, temperature and state of the refrigerant
Only the humidity

48

Difficult

What are CO₂ saturation tables used for?


To determine the oil quantity
To regulate the compressor
To measure humidity
To determine the relationship between temperature and pressure at saturation

49

Difficult

What does the CO₂ saturation state mean?


A state in which the refrigerant is only a gas
Dry ice state
Equilibrium between the liquid and vapour phases
A state of high pressure

50

Difficult

When can dry ice (solid CO₂) form?


At high pressure
During normal operation of the system
In the event of a sudden drop in pressure and temperature below the triple point
At high temperature

51

Difficult

What risks are associated with the formation of dry ice in a CO₂ system?


Pressure reduction
Blocked pipes and system damage
No risk
Improved efficiency

52

Difficult

How does the CO₂ pressure change as the temperature rises?


Rises sharply
It first decreases, then increases
It remains the same
It decreases

53

Difficult

Why is understanding the log(p)-h graph particularly important for CO₂?


It doesn’t matter
As CO₂ systems operate in different modes (sub- and transcritical) and require detailed analysis
It only applies to NH₃
It is only used for design purposes

54

Difficult

What happens to CO₂ above the critical point?


It transitions to a supercritical state (no distinction between liquid and gas)
It turns into a liquid
It ceases to conduct heat
It turns into a solid

55

Difficult

Why do CO₂ systems require precise pressure control?


Because there are no valves
Due to significant pressure changes with temperature fluctuations
Due to low pressures
They do not require control

56

Difficult

What is the main difference between a dry evaporator and a flooded evaporator?


A dry evaporator is filled with refrigerant liquid, whilst a flooded evaporator is filled with gas
A dry evaporator does not require an expansion valve, whereas a flooded one does
A dry evaporator allows the entire refrigerant to evaporate in the pipe upstream of the compressor; in a flooded evaporator, part of the refrigerant remains in a liquid state within the evaporator
A dry evaporator has a lower operating pressure than a flooded one

57

Difficult

What is the typical pressure in deep-freezing systems (below −40 °C) for an evaporator in a system using R717?


Positive pressure, in the range of 5–10 bar
A pressure varying between 10 and 20 bar
Atmospheric pressure, approximately 1 bar
Negative pressure (vacuum), below 0 bar

58

Difficult

Why are PFAS substances formed as a result of the decomposition of certain F-gases problematic?


They are readily biodegradable, so they only pollute the environment for a short time
They are climate-neutral
They cause rapid cooling of the atmosphere
They are persistent, accumulate in the environment and may be toxic

59

Difficult

What is the basic requirement when charging a system with R717 (NH₃)?


Charging must only take place at temperatures below 0°C
Charging should take place in a well-ventilated area using appropriate personal protective equipment
Charging can be carried out without personal protective equipment
NH₃ can be charged together with air

60

Difficult

How should oil be handled in systems using R717?


Oil can be mixed with any refrigerant
The oil should be checked regularly and any excess removed from the lower parts of the units to prevent reduced heat transfer and leaks
The oil does not require any monitoring
Oil has no effect on the system’s operation

61

Difficult

What is the correct procedure for recovering R717 from a system?


The gas can be released into the atmosphere
Recovery is not required
The refrigerant must be recovered into suitable, leak-proof tanks designed for NH₃
The refrigerant can be drained into the sewer system

62

Difficult

How should R717 (NH₃) be stored?


In unmarked plastic containers
In sealed, labelled containers, in a cool and well-ventilated place
Near heat sources
In any open containers

63

Difficult

What should be done in the event of R717 contamination?


Release into the atmosphere
Continue to use without restriction
Add water to dilute it
The refrigerant must be purified or sent for disposal in accordance with regulations

64

Difficult

What is the main hazard associated with an R717 leak during maintenance work?


Toxic to humans and may cause chemical burns
No risk whatsoever
Damage to electrical equipment only
Increased cooling efficiency

65

Difficult

What action should be taken if an NH₃ leak is detected?


Increase the pressure in the system
Evacuate personnel immediately and remove the source of the leak, if it is safe to do so
Ignore it and carry on working
Close your eyes and carry on working

66

Difficult

What role do scrubbers play in NH₃ systems?


Neutralises ammonia through absorption in a liquid (e.g. water)
They increase the pressure in the system
They store the refrigerant
They are used to measure temperature

67

Difficult

How should the system be prepared before filling with R717?


There is no need to check it
Check for leaks, remove air and moisture, and create a vacuum
Simply start it up
The pressure must be increased above the standard level

68

Difficult

What are the transport requirements for R717?


Transport is not subject to regulations
It can be transported without labelling
Must be transported in suitable, labelled containers in accordance with ADR regulations
It can be transported in open containers

69

Difficult

What personal protective equipment is required when working with NH₃?


No requirements
Only a safety helmet
Workwear only
Safety goggles, gloves and respiratory protective equipment

70

Difficult

What is the main characteristic of R744 (CO₂) refrigeration systems?


Very high operating pressures
No need for regulation
Low energy efficiency
Low operating pressures

71

Difficult

What are the requirements for piping materials in CO₂ systems?


It does not matter
They must be able to withstand high pressures (e.g. high-grade steel)
They may be made of any material
They must be made exclusively from plastics

72

Difficult

How does a booster system work in CO₂ installations?


It reduces the amount of refrigerant
It is used to store the refrigerant
It reduces the pressure in the evaporator
It utilises two stages of compression (low and medium pressure) in a single system

73

Difficult

What is the function of high-pressure control valves in CO₂ systems?


They control the pressure on the high-pressure side and optimise system operation
They lower the evaporator temperature
They are used to store the refrigerant
They regulate oil flow

74

Difficult

Why is pressure optimisation in CO₂ systems crucial?


It reduces the amount of refrigerant
It doesn’t matter
It reduces the ambient temperature
It enables the system to achieve maximum energy efficiency

75

Difficult

What role do parallel-operating compressors play in CO₂ systems?


They enable gas recovery from the medium-pressure stage and improve efficiency
They increase energy consumption
It does not matter
They lower the ambient temperature

76

Difficult

How does an ejector work in a CO₂ system?


It lowers the evaporator temperature
It uses the energy of the higher-pressure refrigerant to raise the pressure of the refrigerant from the lower stage, which improves efficiency
It increases the amount of refrigerant
Stores the refrigerant

77

Difficult

What is the function of liquid ejectors in CO₂ systems?


They raise the refrigerant temperature
They reduce atmospheric pressure
They increase the amount of oil
They assist with liquid recovery and improve evaporator feed

78

Difficult

What are the characteristics of partially flooded systems in CO₂ systems?


The absence of liquid in the evaporator
Lack of regulation
Low operating pressure
The presence of liquid in the evaporator, which improves heat transfer and efficiency

79

Difficult

What is the main risk associated with static pressure in CO₂ systems?


A drop in temperature
Increased efficiency
A rise in pressure resulting from the refrigerant heating up whilst at rest
A decrease in refrigerant quantity

80

Difficult

How can standstill pressure in CO₂ systems be reduced?


By increasing the temperature
By increasing the refrigerant charge
By using parallel compressors and external cooling systems
By shutting down the system completely

81

Difficult

What does ‘stagnation’ of a refrigeration system mean in the context of CO₂?


A drop in temperature
A lack of refrigerant flow, which can lead to increased pressure and safety risks
Improved efficiency
Normal system operation

82

Difficult

Why do CO₂ systems require more advanced automation than traditional systems?


Because there are no valves
They do not require automation
Due to low pressures
Due to the need for precise control of pressure and temperature

83

Difficult

What must be included on the label of a cylinder containing a flammable refrigerant?


Information about the cylinder owner
Net weight only
Agent name only
The name of the refrigerant, the hazard symbol and basic safety information

84

Difficult

Why does the absence of a ‘flammable agent’ label on the system pose a significant hazard?


It has no significant impact on safety
It may lead to the use of tools that are a source of ignition
It may lead to the incorrect selection of oil
It reduces the system’s efficiency

85

Difficult

Which set of information on the label of a flammable agent cylinder is crucial from a safety perspective?


Gross weight and batch number
Name of the substance, hazard pictogram, UN number
Manufacturer’s name and country of origin
Cylinder colour and date of manufacture

86

Difficult

What is the requirement regarding the labelling of an installation containing a flammable substance?


Colour-coding of pipes is sufficient
Labelling is required only in technical rooms
The labelling must indicate the type of substance and the flammability hazard
Labelling is not required for hermetically sealed systems

87

Difficult

What are the potential consequences of using unsuitable connections in a system containing a flammable substance?


No impact on safety
Risk of leakage and the formation of an explosive mixture
Merely installation difficulties
Merely a reduction in efficiency

88

Difficult

What is the purpose of installing gas detectors in a room with a refrigeration system?


Early detection of refrigerant leaks and prevention of health risks
Monitoring pipe pressure
Regulating compressor capacity
Measuring the refrigerant temperature

89

Difficult

How often should gas detection sensors in the service room be checked?


Once every 5 years
In accordance with the manufacturer’s instructions and applicable health and safety regulations
Before each start-up of the unit
Only after a leak has occurred

90

Difficult

Where should a gas detector be positioned in accordance with EN 378?


Near the control panel
On the ceiling if the gas is lighter or heavier than air; near the floor if it is lighter or heavier
Only at the entrance to the room
Anywhere in the room

91

Difficult

How should an employee respond when a gas alarm is triggered?


Leave the room immediately and notify their supervisor
Carry on working until they see a leak
Reduce the pressure in the system
Switch off the system and wait for the alarm to stop

92

Difficult

What safety checks should be carried out when installing a new refrigeration system?


The presence of health and safety signage, adequate ventilation and gas detectors
The colour of pipes and hoses
Is the air filter new?
Only the compressor power

93

Difficult

Gas detectors should be installed in rooms where:


Ventilation is natural
Any refrigerant is present, regardless of the quantity
The room is less than 5 m²
The amount of refrigerant exceeds a specified permissible threshold

94

Difficult

What is the minimum number of emergency exits in a plant room (refrigeration plant room) and how should they be signposted?


Exits do not need to be signposted if the room is small
One exit with an information sign about the refrigerant
At least two exits, but signage is optional
One exit, clearly marked in the direction of escape

95

Difficult

Which measure, when installing a system using a flammable refrigerant, improves its energy efficiency?


Restriction of ventilation
Thorough leak testing and vacuuming
No leak test
Increasing the refrigerant charge

96

Difficult

How do leaks affect systems using flammable refrigerants?


They lower the temperature
They improve efficiency
Have no effect
They cause refrigerant loss, reduced efficiency and a fire hazard

97

Difficult

Why is it important to limit the amount of refrigerant in HC systems?


It increases efficiency
It has no effect
It lowers the temperature
It reduces the risk of explosion and improves the system’s operational safety

98

Difficult

Why is the cleanliness of heat exchangers in HC systems important?


It increases the pressure
It doesn’t matter
It improves heat transfer and reduces energy consumption
Causes leaks

99

Difficult

What maintenance measures improve the efficiency of a system using a flammable refrigerant?


Lack of servicing
Disabling safety devices
Increasing the refrigerant charge
Regular checks for leaks and operating parameters

100

Difficult

How does the correct selection of components affect a system using a flammable refrigerant?


It lowers the temperature
It increases the amount of refrigerant
It ensures safe and optimal operation and minimises energy losses
It doesn’t matter

101

Difficult

Why is it important to use the correct service tools in HC systems?


Causes leaks
It ensures operational safety and reduces refrigerant losses
It increases energy consumption
It doesn’t matter

102

Difficult

How does pipe insulation affect the efficiency of systems containing HC?


It doesn’t matter
It reduces energy losses and improves efficiency
It increases the pressure
Causes leaks

103

Difficult

Which safety class applies to R744?


B2L
A2
A3
A1

104

Difficult

In an R744 system operating in supercritical mode, the refrigerant entering the evaporator expansion valve is...


A two-phase mixture at intermediate pressure
A subcooled liquid
A supercritical fluid
Saturated vapour at intermediate pressure

105

Difficult

In R744 supercritical systems, the gas cooler outlet valve controls:


The inlet temperature to the gas cooler
The outlet temperature of the gas cooler
The pressure in the gas cooler
The gas cooler fans

106

Difficult

Which statement best describes the behaviour of R717 and mineral compressor oil?


R717 does not mix with compressor oil, so the oil remains in the system on the low-pressure side as a layer beneath the R717
R717 does not mix with compressor oil, so the oil remains in the system on the high-pressure side as a layer above the R717
In an R717 system, a return oil line cannot be used because the oil is too hot
R717 mixes very well with compressor oil and easily returns to the compressor

107

Difficult

What is the main reason for using K65 copper tubing in some R744 systems?


They have good low-temperature performance
They come in a wider range of diameters
They can withstand higher pressures
They bend easily

108

Difficult

Which of the following statements is correct regarding the installation of Schrader valves?


Schrader valves must not be used in R744 systems
All Schrader valve cores are suitable for all refrigerants
Hydrocarbons leak through Schrader valves
When brazing the valve body to the system, the core must be removed, then refitted and tightened to the correct torque

109

Difficult

Which refrigerant can be detected using phenolphthalein paper?


R1234ze
R1270
R717
R744

110

Difficult

How does a refrigerant shortage affect the high-pressure side of the system (without discharge pressure regulation)?


The discharge pressure will be lower, and the subcooling will be lower
Discharge pressure will be lower, subcooling will be higher
Discharge pressure will be higher, and the degree of subcooling will be higher
Discharge pressure will be higher, and the degree of subcooling will be lower

111

Difficult

What is the benefit of using helium as a tracer gas in nitrogen during a pressure test?


It is non-flammable
It has a higher pressure than pure nitrogen
It has smaller molecules and diffuses more easily
It has a distinct odour

112

Difficult

Why should an R744 system that has been drained be initially charged with the refrigerant in gaseous form?


To prevent the drain valve from opening
To prevent damage to the compressor
To ensure that R744 is charged slowly
To prevent the formation of dry ice

113

Difficult

If an R744 system contains moisture because it has not been properly drained, what is the likely consequence?


The formation of carbonic acid, which will cause damage to the system
Reduced cooling capacity
Excessively high discharge pressure
The formation of hydrogen fluoride, which will decompose into hydrofluoric acid and damage the compressor

114

Difficult

Which system may require manual oil recovery?


R744 cascade system
Secondary system using R744
An R717 system
Supercritical ‘booster’ system using R744

115

Difficult

The pressure of R744 at a saturation temperature of 20 °C is approx.


25 bar g
14 bar g
56 bar g
90 bar g

116

Difficult

Which refrigerant is lighter than air?


R744
R1234ze
R1270
R717

117

Difficult

What hazards are associated with a Class A3 safety agent?


High flammability, lower toxicity
Lower toxicity, does not propagate flames
Slightly flammable, lower toxicity
High toxicity, does not propagate flames

118

Difficult

18 What is the GWP of R32 (according to AR4)?


3945
6
675
0

119

Difficult

What factors are taken into account when determining the maximum charge for comfort air-conditioning/heating applications?


Lower flammability limit, room volume
Practical limit, height of the indoor unit, floor area
Practical limit, room volume
Lower flammability limit, height of the indoor unit, floor area

120

Difficult

What compressor displacement is required for R1270, relative to R404A compressors for the medium-temperature range (cold store)?


Similar
600%
150%
50%

121

Difficult

At an ambient temperature of 25°C, the standby pressure in the low-pressure stage of an R744 cascade system will typically be…


27.5 bar g
Higher than the maximum permissible pressure in the low-pressure stage
The same as the high-pressure setting on the pressure switch
The same as the pressure set on the relief valve

122

Difficult

What is the correct definition of critical temperature?


The temperature above which there are no distinct liquid and gaseous phases
The temperature at which a substance changes from a gaseous to a solid state
The temperature at which the vapour pressure of a liquid is equal to the ambient pressure surrounding the liquid
The temperature at which, for certain substances, electrical resistance is zero

123

Difficult

In a supercritical system, under supercritical conditions, the working fluid in the gas cooler


it loses heat when its pressure drops
loses heat during a phase change
it loses heat as its temperature drops
loses heat at constant temperature and pressure

124

Difficult

R717 is highly corrosive to


copper
titanium
stainless steel
aluminium

125

Difficult

What is the effect of repeatedly opening the relief valve?


The valve remains fully open continuously
The relief pressure drops
The valve will not open
The relief pressure rises

126

Difficult

What is the relationship between the pressure (P) and temperature (T) of nitrogen at the start (1) and end (2) of the leak test?


P2 = (P1 × T2)/T1
P2 = T2/(P1 × T1)
P2 = (P1 × T1)/T2
P2 = T1/(P1 × T2)

127

Difficult

What is the recommended alarm level for fixed leak detection systems for R717?


50,000 ppm
500 ppm
5,000 ppm
500,000 ppm

128

Difficult

Why are compressors with a separate electric motor most commonly used in R717 (NH₃) refrigeration systems?


To reduce the condensing pressure
Because NH₃ reacts with the motor windings and hermetic compressors are not used
Because compressors with a separate motor are cheaper
To increase the amount of refrigerant in the system

129

Difficult

Which type of compressor is most commonly used in large ammonia systems?


A reciprocating or screw compressor
Hermetic scroll
Rotary vane compressor
Diaphragm compressor

130

Difficult

How is the capacity of a piston compressor regulated in NH₃ systems?


By reducing the refrigerant charge
By increasing the condensing pressure
By unloading the cylinders or changing the rotational speed
Solely by adjusting the oil volume

131

Difficult

How is the capacity of a screw compressor most commonly controlled?


By closing the suction valve
By using a slide valve
By changing the type of oil
By adjusting the oil level

132

Difficult

When is two-stage compression used in NH₃ systems?


At very low vapour pressures and high pressure differentials
Only with water-cooled condensers
Exclusively in small systems
At small temperature differences

133

Difficult

What is the advantage of two-stage compression over single-stage compression?


No need for a separator
Lower efficiency
Higher energy consumption
Higher efficiency and lower discharge temperature

134

Difficult

How does an evaporative condenser used in NH₃ systems work?


Operates without a fan
It does not require a water supply
It transfers heat only to the air
It utilises the evaporation of water to increase cooling efficiency

135

Difficult

What is the function of the liquid separator in an NH₃ system?


Increases the discharge temperature
Regulates the condensing pressure
It separates oil from the refrigerant
It prevents liquid from entering the compressor

136

Difficult

What is the purpose of monitoring the liquid level in the separator?


To maintain the correct refrigerant level and prevent the compressor from flooding
To reduce the condensing temperature
To increase the oil volume
To control the condenser fan

137

Difficult

What is the role of the float switch in NH₃ systems?


It monitors the liquid level in the tank or separator
It regulates the condensation temperature
It controls the fan’s operation
It is used to detect leaks

138

Difficult

What is a thermosiphon in NH₃ systems?


An oil circulation system utilising differences in pressure and temperature
A type of safety valve
A type of evaporator
A defrosting device

139

Difficult

Why are oils that are immiscible with the refrigerant used in NH₃ systems?


Because the oil mixes only with water
Because NH₃ does not mix with most compressor oils
To reduce the pressure
To increase the amount of refrigerant

140

Difficult

What is the main function of an oil separator in NH₃ systems?


To separate the oil from the refrigerant and return the oil to the compressor
To increase fan efficiency
To lower the condensation temperature
Removing moisture from the system

141

Difficult

Which NH₃ system features direct evaporation of the refrigerant in the evaporator?


Thermosiphon system
Direct expansion (DX) system
Glycol system
Indirect system

142

Difficult

What is the characteristic feature of a flooded evaporator system?


No level control is required
The evaporator is filled exclusively with vapour
No separator is used
The evaporator contains a large amount of liquid, which improves heat transfer

143

Difficult

What is the main difference between a direct and an indirect system?


In an indirect system, no compressor is used
In a direct system, there is no evaporator
In an indirect system, NH₃ flows directly into the space being cooled
In an indirect system, NH₃ cools an intermediate medium (e.g. glycol), which in turn cools the load

144

Difficult

Which parts of refrigeration systems must be inspected on a mandatory and regular basis in accordance with EU Regulation 1516/2007?


Compressor connections, 2. connections on the liquid refrigerant tank
Fittings, 2. valves, 3. seals, 4. parts/components exposed to vibration, 5. connections at safety devices.
Only compressor connections, as these are subject to vibration.
Connections on the condenser, as there is high pressure and the refrigerant is in liquid form

145

Difficult

In accordance with EU Regulation 1516/2007, there are several methods of leak testing. What are these methods called?


We distinguish between quality control methods for supplied materials and electronic testing methods.
We distinguish between methods for quality control of supplied materials and leak testing methods that do not involve quality control of supplied materials.
We distinguish between physical and chemical methods.
We distinguish between direct and indirect methods of leak detection.

146

Difficult

In accordance with EU Regulation 1516/2007, to whom can we entrust the responsibilities for leak testing of refrigeration systems?


The inspection may be carried out by a person employed and appointed by the owner of the installation.
The check may be carried out by a specialist in leak testing.
The test may only be carried out by a competent person with the relevant skills, who holds a certificate attesting to the necessary knowledge in this field. They must also hold a certificate for companies regarding the operation and maintenance of refrigeration equipment charged with F-gases.
The check may only be carried out by a person who has previously carried out such a check.

147

Difficult

In accordance with EU Regulation 1516/2007, what conditions must be met in order to carry out a leak test on refrigeration systems using ultraviolet (UV) light?


A prerequisite for carrying out a leak test using UV is having the appropriate technical resources, the relevant materials supplied, and suitable safety goggles.
A prerequisite for carrying out a leak test using UV is that such a test is technically feasible.
The manufacturer of the refrigeration equipment must confirm that the aforementioned UV method can be used. A UV leak test may be carried out by a qualified person who holds the relevant qualifications (certificate).
A prerequisite for carrying out the inspection is holding the relevant authorisation for pressure testing issued by the UDT.

148

Difficult

In accordance with EU Regulation 1516/2007, which leak testing methods are classified as direct leak testing methods?


Detection of leaks using a handheld leak detector and/or a fixed leak detection system; 2. Detection of leaks using a special dye with UV-fluorescent properties; 3. Detection of leaks using a foaming solution.
Leak test using nitrogen with a tracer gas, an electronic detector and pressure measurement.
Leak test following the creation of a vacuum and leak detection using a foaming solution.
Leak testing by measuring pressure changes and the method of submerging the device/system in water.

149

Difficult

In accordance with EU Regulation 1516/2007, which methods are classified as indirect leak testing methods?


This method is based on the analysis of the following parameters: pressure, temperature, operating pressure, liquid level, oil leakage, etc.
Leak detection using a UV tracer.
It utilises pressure and temperature measurements, as well as an ultrasonic method.
This method is based on electronic leak detection.

150

Difficult

What does a vacuum leak test involve?


With the vacuum pump running continuously, we are able to maintain the required vacuum level in the system.
With the vacuum pump switched on, check whether the pressure in the system rises as a result of a leak.
If the pressure in the refrigeration system were to rise, we switch on the vacuum pump as required.
After switching off the vacuum pump, we check whether the pressure in the system rises

151

Difficult

How often should leak tests be carried out on equipment containing 1.5 kg of R404A refrigerant (5.9 tonnes of CO₂ equivalent)?


Only when servicing the unit.
On initial commissioning.
Once every six months.
At least once every 12 months.

152

Difficult

How often should leak tests be carried out on equipment containing 7 kg of R404A refrigerant (27.45 tonnes of CO₂ equivalent)?


Only when servicing the unit.
On initial commissioning.
Once every six months.
At least once every 12 months.

153

Difficult

In accordance with Regulation (EU) 2024/573 of the European Parliament and of the Council, a fixed leak detection system is required when:


The refrigeration equipment is operated in an enclosed space.
The charge of an F-gas refrigerant in a refrigeration unit is at least 500 tonnes of CO₂ equivalent.
The refrigerant charge of the refrigeration equipment is at least 100 kg of ODS.
The installation of a fixed leak detection system is optional, but it helps to reduce the number of leak checks required on the equipment each year.

154

Difficult

Under Regulation (EC) No 1516/2007 and the F-gas Act, which leak detection methods may not be carried out by a person holding a Category E certificate?


Measuring leaks using a handheld leak detector.
Leak testing using a fluorescent dye.
Visual leak inspection.
Leak detection using a foaming solution.

155

Difficult

According to the current regulation, what sensitivity must a handheld leak detector have?


10 g/year.
3 g/year.
5 g/year.
8 g/year.

156

Difficult

Within what timeframe must a leak test be carried out on a stationary refrigeration system after a leak has been repaired, in accordance with EU Regulation 2024/573 on F-gases?


At any time.
Between 24 hours and 1 month after the repair.
Immediately after the repair.
At the next periodic inspection.

157

Difficult

At what intervals should leak tests be carried out on refrigeration equipment containing more than 500 tonnes of CO₂ equivalent of fluorinated greenhouse gases that does not have a leak detection system installed?


Once every 3 months.
Once every 12 months.
Once every 6 months.
Once a month.