F-Gas English Low GWP

Všetky otázky
HFC | Flammable | CO₂ | NH₃
Ľahké otázky | Stredne ťažké otázky | Ťažké otázky

1

Stredne ťažká

What process takes place in the condenser of a refrigeration system?


The medium flowing through the evaporator (glycol, water) condenses, whilst the refrigerant evaporates.
Hot refrigerant vapour is pumped from the compressor to the condenser, where it is cooled and then condensed. In this heat exchanger, the resulting liquid refrigerant is also slightly subcooled.
The refrigerant releases the heat absorbed in the compressor via the condenser
In the condenser, the refrigerant releases the heat absorbed in the evaporator into the surroundings.

2

Stredne ťažká

What determines the condensation temperature of an air-cooled unit?


On the compressor and discharge temperatures
On the ambient temperature.
On the superheat temperature.
On the evaporation (boiling) temperature.

3

Stredne ťažká

Is energy required when heat is transferred from the condenser to the surroundings?


Yes, but only when using HFC refrigerants.
No, because according to the second law of thermodynamics, thermal energy always flows from a body at a higher temperature to a body at a lower temperature.
The heat flow balances the energy input.
Yes, in every case.

4

Stredne ťažká

What should you pay attention to during the operation of the condenser?


You should ensure the general maintenance of the condenser and keep the heat exchange surfaces clean.
Care should be taken to ensure that the air temperature at the condenser inlet is lower than the air temperature at the condenser outlet.
Pay attention to the fan’s operation and the ambient temperature.
Ensure that the air temperature at the condenser outlet is higher than the condensation temperature.

5

Stredne ťažká

What criteria should be considered when selecting a suitable condenser?


Condensers should be selected based on your own experience, and the condenser’s geometric parameters should be taken into account.
The required capacity of the condenser and the technical specifications declared by the manufacturer must be taken into account.
These include size and the number of fans. The geometric parameters of the condenser must be taken into account.
First and foremost, you should consider the operating noise level of the fans, the diameter of the connection pipes and the colour scheme.

6

Stredne ťažká

How do contaminants (dust, particulates, deposits) affect the performance and efficiency of heat exchange surfaces in condensers?


Contaminants do not significantly affect the efficiency and effectiveness of the heat exchange surfaces in condensers.
Contaminants restrict heat transfer (reducing the heat transfer coefficient) and cause an increase in condensing temperature and pressure, which in turn leads to a reduction in the condenser’s efficiency.
Contaminants increase the heat transfer area and reduce the condensing pressure.
Contaminants restrict heat transfer (reducing the heat transfer coefficient) and cause a reduction in condensing pressure.

7

Stredne ťažká

If an air-cooled condenser becomes contaminated, will the condensation efficiency?


It remains unchanged.
It will increase as a result of the fan speed being raised further.
It will decrease.
It will increase.

8

Stredne ťažká

What can cause frost to form on the evaporator?


An increase in refrigerant flow resistance and a reduction in the refrigerant flow rate through the evaporator.
A reduction in the temperature of the cooled substance.
Frost build-up on the evaporator increases airflow resistance and, consequently, causes the fan motor to work harder.
a drop in cooling capacity.

9

Stredne ťažká

What happens when the evaporation temperature drops?


The condenser fan speed increases.
The compressor’s cooling capacity increases.
The compressor’s cooling capacity decreases.
The discharge temperature decreases.

10

Stredne ťažká

When is defrosting using the refrigerant possible?


Defrosting using the refrigerant is not possible at all.
In the case of air-cooled chillers, only when the air temperature is above 0°C.
Only when using speed-controlled fans.
Never. We use electricity for defrosting (for example, using a special electric heater).

11

Stredne ťažká

When can frost form on the evaporator surface?


In the case of finned evaporators.
Only in the case of air coolers, when the air temperature drops below 0°C.
Frost always forms on air coolers.
Frost forms only when the refrigeration system is operating continuously.

12

Stredne ťažká

In the case of extensive pipework systems, secondary evaporation of the refrigerant can be prevented by...


using larger-diameter pipes.
using smaller-diameter pipes.
additional cooling.
by insulating the pipes between the compressor and the condenser.

13

Stredne ťažká

How does hot gas defrosting of the evaporator work?


We switch on the gas heater directed at the evaporator.
Heated vapour (hot gas) from the compressor is directed into the evaporator piping.
We swap the outlet and inlet sides of the evaporator.
This involves reversing the direction of rotation of the compressor.

14

Stredne ťažká

What is the function of the evaporator in a refrigeration system?


It evaporates the water flowing through the evaporator.
Thanks to the evaporator, the cooled medium transfers heat to the boiling refrigerant.
It ensures that the refrigerant is superheated over the largest possible heat exchange surface area.
It cools the refrigerant.

15

Stredne ťažká

What conditions must be met for the evaporator to be defrosted using electric heaters?


The electric heaters must be positioned in direct contact with the refrigerant so that the refrigerant flowing through the evaporator is at a sufficiently high temperature.
Thanks to the forced air flow created by the fans, the heat from the heaters is transferred to the heat exchanger.
The electric heaters must be positioned beneath the evaporator’s heat exchange surface.
The electric heaters must be in contact with the evaporator’s heat exchange surface (the heater must touch the fins).

16

Stredne ťažká

Refrigerant distributor:


ensures the even distribution of the refrigerant discharged by compressors connected in parallel.
ensures even distribution of the refrigerant to the individual sections of the condenser.
ensures an even distribution of the refrigerant to the individual sections of the evaporator.
acts as a buffer for the refrigerant in the event that the pressure upstream of the expansion valve is exceeded.

17

Stredne ťažká

What are the possible methods of defrosting air coolers?


Electric defrosting, liquid defrosting or defrosting using hot refrigerant vapour.
Electric defrosting only.
Natural defrosting; there are no other effective methods.
Hot gas defrosting.

18

Stredne ťažká

The boiling point increases (and consequently the rate of evaporation increases) if the pressure above the liquid...


Remains constant.
It behaves differently depending on the ambient temperature.
Falls.
Rises.

19

Stredne ťažká

MOP in thermostatic expansion valves stands for:


minimum flow opening.
maximum pressure switch protection.
maximum operating pressure.
self-cleaning of the valve in the event of moisture in the refrigerant freezing.

20

Stredne ťažká

The function of a thermostatic expansion valve (TEV) in a refrigeration system is:


regulating the superheat of the refrigerant leaving the evaporator so that it is at the minimum value.
to maintain a constant suction pressure to the compressor.
to consistently adjust the evaporation pressure in the condenser depending on the temperature of the refrigerant vapour leaving the condenser.
to control the amount of refrigerant supplied to the evaporator depending on the superheat of the vapour leaving that heat exchanger.

21

Stredne ťažká

When using a capillary tube, what type of motor can be used in the compressor?


A motor with high starting torque must be used.
A low-speed motor should be used.
An electronically commutated motor approved for use with the compressor should be used.
A motor with low starting torque can be used.

22

Stredne ťažká

What does the thermostatic expansion valve regulate?


Discharge temperature.
The mass flow of the refrigerant injected into the evaporator.
Evaporation pressure after.
Cooling.

23

Stredne ťažká

The refrigerant absorbs heat when...


sublimates
it evaporates.
freezes.
it condenses.

24

Stredne ťažká

In the case of a thermostatic expansion valve, the manufacturer specifies...


  ...the degree to which the valve is filled with refrigerant liquid.
...the static superheat of the valve.
...the superheat value during valve operation.
…the degree of refrigerant expansion.

25

Stredne ťažká

How do we charge a new or repaired system with refrigerant when it is fitted with an expansion valve


in any way.
behind the condenser to the liquid refrigerant receiver.
Charging with refrigerant takes place during operation via the outlet connection of the refrigerant capillary tube.
to the suction side of the compressor.

26

Stredne ťažká

What does a thermostatic/electronic expansion valve regulate?


Condenser subcooling by adjusting the condensing pressure.
The evaporation pressure, closing when it falls below the setpoint temperature.
The number of revolutions of the compressor per unit of time.
The amount of refrigerant by controlling the evaporator superheat.

27

Stredne ťažká

What does the MOP function in expansion valves mean?


This means that these expansion valves are set to a specific suction pressure.
It means that these expansion valves are set to limit the maximum operating pressure.
This means that these expansion valves are set to limit subcooling.
This means that these expansion valves are set to prevent overheating.

28

Stredne ťažká

The lower the temperature of the liquid refrigerant upstream of the expansion valve,


  ...the lower the theoretical coefficient of cooling efficiency qo will be, whilst the cooling capacity Qo remains unchanged.
... the higher the theoretical coefficient of cooling capacity qo will be, and the greater the cooling capacity Qo will be.
...the lower the theoretical coefficient of refrigeration efficiency qo will be, and the lower the refrigeration capacity Qo will be.
...the lower the theoretical coefficient of cooling efficiency qo will be, and the lower the system’s energy efficiency will be.

29

Stredne ťažká

The MOP point in the expansion valve, due to the maximum evaporation temperature of the refrigeration system, ...


...must be approximately 5 K lower.
The value of the MOP point is irrelevant.
...must be approximately 7 K higher.
...must be approximately 7 K lower.

30

Stredne ťažká

What is the function of the suction pressure regulator?


It limits the suction pressure and protects the compressor from excessively high suction pressure.
It maintains the suction pressure at a constant level.
To maintain the suction pressure at the highest possible level.
It prevents a drop in suction pressure and, if necessary, shuts down the refrigeration system.

31

Stredne ťažká

What is the function of the valve regulating water flow through the condenser?


To maintain the condensing pressure at the highest possible level.
To maintain the water temperature at the highest level.
To maintain the condensing pressure at the lowest possible level.
To maintain the condensing pressure at a constant level.

32

Stredne ťažká

The use of a refrigerant distributor requires a thermostatic expansion valve …


… with an adsorption-type sensor filling.
… with external pressure equalisation.
… with a MOP function.
… with internal pressure equalisation.

33

Stredne ťažká

What properties should good insulation materials have?


It must be able to absorb large amounts of moisture.
It must have a good antistatic coating
It must have a low thermal conductivity.
It must have a high thermal conductivity.

34

Stredne ťažká

When do we encounter the superheated state?


It is a condition in which the compressor motor temperature rises excessively.
It is the temperature difference between the evaporation temperature and the ambient temperature.
This is a state that arises as a result of the temperature difference between the suction side and the discharge side of a compressor.
This is the temperature difference between the actual vapour temperature and the vapour temperature at saturation.

35

Stredne ťažká

How can you check whether the liquid refrigerant is reaching the expansion valve without vapour bubbles?


We check this using a sight glass.
We check using a liquid pressure gauge.
We are unable to check this.
We check using a pressure gauge fitted on the discharge side of the compressor.

36

Stredne ťažká

The liquid lines are located...


between the evaporator and the compressor.
between the compressor and the condenser.
between the evaporator and the regenerative heat exchanger.
between the condenser and the liquid receiver.

37

Stredne ťažká

What is the function of the liquid receiver in a refrigeration system?


When an installation technician does not know the exact amount of refrigerant required, the tank serves as a safety reserve for the entire refrigeration system.
The tank is used to store and ensure an adequate supply of refrigerant in the event of fluctuations in the thermal load of the refrigeration system.
The reservoir is used to further cool the liquefied refrigerant leaving the condenser.
The tank is used to collect the liquid refrigerant and excess oil in the system.

38

Stredne ťažká

What is the purpose of the liquid refrigerant reservoir?


The tank is required during maintenance work, when there is a temporary need to store the refrigerant that has been circulating in the refrigeration system up to that point.
The tank is used to further cool the liquefied refrigerant leaving the condenser.
The tank is used to collect the liquid refrigerant and excess oil in the system.
When an installation technician does not know the exact amount of refrigerant required, the tank serves as a safety reserve for the entire refrigeration system.

39

Stredne ťažká

Where should the liquid receiver be installed?


It should be fitted after the evaporator.
It should be installed downstream of the condenser, upstream of the expansion valve.
It should be fitted between the compressor and the condenser.
It should be fitted just before the compressor.

40

Stredne ťažká

What is the function of the suction pressure regulator fitted to the suction pipe when the compressor starts up?


It regulates the evaporation pressure.
It closes when the suction pressure upstream of the compressor drops.
It opens when the suction pressure upstream of the compressor drops.
It regulates the condensing pressure.

41

Stredne ťažká

The use of microchannel heat exchangers, compared with conventional heat exchangers made of copper tubes and fins, results in:


An increase in the amount of refrigerant in the system and an increase in condensing pressure.
A reduction in the amount of refrigerant and an increase in energy efficiency.
A reduction in the system’s energy efficiency.
There is no effect whatsoever on either the amount of refrigerant or energy efficiency.

42

Stredne ťažká

Which refrigerants belong to the HFC group?


R22, R401A.
R134a, R32, R22, R507A, R290.
R134a, R404A, R507A, R410A.
R11, R12, R502.

43

Stredne ťažká

Which refrigerants belong to the HFO group?


R22, R12.
R1234yf, R1234ze.
R134a, R404A.
R134a, R290.

44

Stredne ťažká

What are the characteristics of R410A refrigerant compared to R407C refrigerant?


The saturation pressure of R407C refrigerant is much higher than that of R410A.
The saturation pressure of both refrigerants is roughly the same.
The saturation pressure of R407C is 150% higher than that of R410A.
The saturation pressure of R410A refrigerant is higher than that of R407C.

45

Stredne ťažká

What does the TEWI parameter define?


It is the total (global) greenhouse gas equivalent – this indicator takes into account the refrigerant’s direct capacity to contribute to the greenhouse effect and its indirect impact on it through the energy consumption (during the production of which CO₂ is generated) by the refrigeration unit in operation.
This is a parameter defining the ozone layer’s ability to recover (regenerate).
This is a parameter that quantifies the impact of refrigerants on the ozone layer.
It is the global warming potential, expressed in terms of carbon dioxide (CO₂), over a 100-year time horizon.

46

Stredne ťažká

What are the characteristics of R452A refrigerant compared to R404A?


It is a non-flammable refrigerant, a mixture from the HFC/HFO group with thermodynamic properties similar to those of R404A and a GWP approximately 45% lower than that of R404A.
The temperature glide of R452A is half that of R404A.
It is a flammable and toxic homogeneous refrigerant from the HFC group.
Both refrigerants are homogeneous refrigerants with no temperature glide.

47

Stredne ťažká

What is the distinguishing feature of R1234yf compared to R134a?


greater flammability.
greater toxicity.
a higher boiling point at standard pressure.
A higher critical temperature.

48

Stredne ťažká

Compared to R134a, the refrigerant CO₂ is characterised by?


It has identical thermodynamic properties and can be used as a drop-in replacement for R134a.
Unlike R134a, it is an azeotropic mixture.
It has a temperature slip of 7K greater than R134a.
It has a lower critical temperature, higher operating pressures and greater volumetric efficiency, allowing for the use of a smaller quantity of refrigerant compared to R134a.

49

Stredne ťažká

The following are not classified as fluorinated greenhouse gases:


Sulphur hexafluoride (SF6).
Hydrofluorocarbons (HFCs).
Perfluorocarbons (PFCs).
Carbon dioxide (CO₂).

50

Stredne ťažká

What is the greenhouse effect?


It causes the thermal radiation emitted by the Earth to be trapped in the upper atmosphere.
It alters the composition of the atmospheric air.
It causes an increase in temperature close to the Earth’s surface (up to 10 metres above the surface).
It lowers the average surface temperature of the Earth.

51

Stredne ťažká

What is R1270?


Propene
Isobutane
Butane
Propylen

52

Stredne ťažká

How do refrigeration systems contribute to the greenhouse effect, i.e. the rise in atmospheric temperature at the Earth’s surface?


As a result of oil being emitted into the atmosphere by the condenser and filter
Refrigeration equipment emits CO₂ both directly and indirectly.
Through the leakage of refrigerant into the environment.
Indirectly (through energy consumption) and directly (through the emission of refrigerants into the atmosphere)

53

Stredne ťažká

What is the greenhouse effect, also known as the greenhouse phenomenon?


It is the phenomenon of heat being trapped in the Earth’s atmosphere (making it difficult for heat to radiate out of the Earth’s atmosphere).
The filtering out of solar radiation.
This is the formation of a layer that traps only the heat generated by the combustion of fuel in aeroplanes.
The absorption of radiation reaching the Earth’s surface.

54

Stredne ťažká

Which EU regulation is currently the primary piece of legislation governing the use of fluorinated greenhouse gases (F-gases) in the European Union?


Regulation (EU) No 517/2014
Directive 2009/125/EC
Regulation (EU) 2015/1188
Regulation (EU) 2024/573

55

Stredne ťažká

What is the main objective of Regulation (EU) 2024/573?


Prevention of F-gas emissions and the achievement of the EU’s climate targets
Standardising metal recycling standards
To facilitate the import of electrical appliances
To reduce taxes on refrigeration equipment

56

Stredne ťažká

What are the obligations of manufacturers of refrigeration appliances in the context of ecodesign, and which regulation governs them?


Manufacturers are only required to use energy labels, and this is regulated by Regulation (EU) 2024/573
Manufacturers are only required to declare the quantity of F-gas used, in accordance with Regulation (EU) No 517/2014
The manufacturer must ensure minimum energy efficiency, reparability and recyclability of equipment, as regulated by Regulation (EU) 2019/2019
Manufacturers must comply solely with ISO 9001 standards, without any link to EU regulations

57

Stredne ťažká

What is the main objective of the Ecodesign Directive?


To increase sales of electrical appliances in the EU
To facilitate the import of products from outside the EU
To standardise the appearance of products in the EU
Reducing the negative environmental impact of products by improving energy efficiency, durability and recyclability

58

Stredne ťažká

What is the function of a ball valve in a refrigeration system?


It prevents excessive pressure build-up in the system
It measures the moisture content of the refrigerant
Enables the refrigerant flow to be completely shut off
It regulates the temperature of the refrigerant

59

Stredne ťažká

How do certain substances or gases contribute to the greenhouse effect?


Certain substances trap the thermal radiation that the Earth should radiate into the atmosphere. In this way, the Earth gradually warms up and the greenhouse effect occurs.
When released into the atmosphere, certain substances cause the air to heat up as a result of reactions with the oxygen and nitrogen contained in the air.
Some substances damage the ozone layer
Certain substances limit the impact of the Sun’s ultraviolet radiation on the Earth’s surface.

60

Stredne ťažká

What is the purpose of the sight glass in a refrigeration system?


To shut off the flow in the event of an emergency
For visual assessment of the presence of refrigerant and oil, and for monitoring moisture levels
To measure the condenser temperature
To regulate compressor pressure

61

Stredne ťažká

What is the function of the temperature regulator in a refrigeration system?


It restricts oil flow
To maintain a constant pressure in the compressor
Controls the operation of the compressor and valves to maintain the set temperature
It drains excess refrigerant into the receiver

62

Stredne ťažká

What is the purpose of oil level regulators in a refrigeration system?


They drain off excess refrigerant
Maintains the correct oil level in the compressor
They control the pressure in the condenser
They control the evaporator temperature

63

Stredne ťažká

What is the function of the refrigerant receiver in the system?


Regulates the oil flow
It maintains a constant pressure in the system
It controls the evaporator temperature
Stores excess refrigerant and facilitates the detection of leaks

64

Stredne ťažká

What is the role of the manifold thermometer in the refrigeration system?


It monitors the moisture content of the refrigerant
Relieves pressure in the system in the event of excessive pressure
Controls the oil level
Measures the refrigerant temperature at the compressor inlet and outlet, which helps to identify leaks

65

Stredne ťažká

What is the role of the defrost control valves?


They control the pressure in the compressor
Protect the evaporator from excessive icing and reduce the risk of leaks
They are used to monitor the moisture content of the refrigerant
They drain off excess oil

66

Stredne ťažká

Where can I find lists detailing fluorinated greenhouse gases (F-gases)?


In Regulation (EU) No 2024/573 of the European Parliament and of the Council
In the Regulation of the Minister for the Economy on the introduction of a list of fluorinated greenhouse gases.
In the Act on Ozone-Depleting Substances and Certain Fluorinated Greenhouse Gases.
In the Vienna Convention for the Protection of the Ozone Layer.

67

Stredne ťažká

Where can I find the lists specifying controlled substances?


In the current Act on Ozone-Depleting Substances and Certain Fluorinated Greenhouse Gases.
In the Regulation of the Minister for the Environment on the list of controlled substances.
In the Vienna Convention for the Protection of the Ozone Layer.
In Regulation (EU) No 2024/590 of the European Parliament and of the Council.

68

Stredne ťažká

Why is ammonia (NH₃) considered a toxic refrigerant?


It is highly irritating to the respiratory tract and toxic if inhaled
It is colourless and odourless, so it is difficult to detect
It does not react with water, which makes it difficult to neutralise
It is flammable and can form explosive mixtures with air

69

Stredne ťažká

Where and by when should annual reports on ODS and F-gases be submitted?


Reports must be submitted by the end of the relevant calendar year, using a special form at the regional branch of the Office of Technical Inspection (UDT)
Reports for the previous year must be submitted by 31 January electronically by completing the special forms available in the central register of operators ‘CRO’.
Reports for the previous year must be submitted by 31 March of the relevant year electronically to the Ministry of the Environment.
Reports on ODS and F-gases for the previous year must be submitted by 28 February of the following year, via the IT system available in the reports database at the Office for the Protection of the Ozone Layer and Climate (BOWOiK) on the ICHP website.

70

Stredne ťažká

Which measure has the greatest impact on improving the compressor’s energy efficiency during installation?


Correctly create a vacuum and remove moisture from the system
Installation without filters
Increasing the amount of refrigerant
Installation without a leak test

71

Stredne ťažká

How does regular monitoring of the oil level affect the compressor’s operation?


It has no effect
It reduces cooling capacity
Ensures proper lubrication and improves energy efficiency
Causes a rise in pressure

72

Stredne ťažká

How do system leaks affect the compressor’s energy efficiency?


Have no effect
These cause a drop in performance and an increase in energy consumption
They lower the operating temperature
They improve efficiency

73

Stredne ťažká

Regulation (EC) No 2024/590 relates to:


Ozone-depleting substances.
The conditions for obtaining F-gas certificates by companies carrying out the recovery and reclamation of waste refrigerants.
Health and safety at work during the recovery of refrigerants.
Alternative refrigerants serving as substitutes for fluorinated greenhouse gases.

74

Stredne ťažká

What is the significance of regulating suction and discharge pressure?


Causes leaks
Helps maintain optimal operating conditions for the compressor
Increases oil consumption
It has no effect on efficiency

75

Stredne ťažká

What maintenance measure reduces the compressor’s energy consumption?


Lack of servicing
Regular replacement of filters and dryers
Increasing the refrigerant charge
Disabling safety devices

76

Stredne ťažká

How does the presence of air in the refrigeration system affect performance?


It has no effect
It improves efficiency
Reduces energy consumption
Leads to increased pressure and reduced efficiency

77

Stredne ťažká

What role do control systems (e.g. regulators) play in compressor efficiency?


Causes leaks
It increases the amount of refrigerant
Enables optimisation of operation and a reduction in energy consumption
It doesn’t matter

78

Stredne ťažká

How does refrigerant superheat at the compressor suction affect performance?


It always improves performance
It has no effect
It only causes a drop in temperature
Excessive overheating reduces efficiency and increases energy consumption

79

Stredne ťažká

How does the correct layout of the system affect efficiency?


It causes the temperature to rise
It doesn’t matter
It increases the pressure
Shortens flow paths and reduces energy losses

80

Stredne ťažká

How important is pipe insulation?


It has no effect
Reduces heat loss and improves energy efficiency
Causes a rise in pressure
It increases energy consumption

81

Stredne ťažká

Which measure most improves the condenser’s energy efficiency?


Contamination of the heat exchange surface
Restricted airflow
Regular cleaning of heat exchange surfaces
Increasing the amount of refrigerant

82

Stredne ťažká

How does a dirty condenser affect the operation of the refrigeration system?


It has no effect
Causes an increase in pressure and energy consumption by the compressor
It lowers the condensing pressure
It improves efficiency

83

Stredne ťažká

Why is adequate airflow through an air-cooled condenser important?


Causes a drop in pressure
Insufficient airflow reduces efficiency
It doesn’t matter
Ensures effective heat dissipation and improves energy efficiency

84

Stredne ťažká

Which refrigerants cause damage to the ozone layer?


All refrigerants that contain fluorine and hydrogen in their molecules.
All refrigerants that contain chlorine or bromine in their molecules.
All refrigerants that contain carbon in their molecular structure.
All refrigerants that are hydrocarbon derivatives.

85

Stredne ťažká

How does the presence of limescale in a water-cooled condenser affect performance?


Impairs heat exchange and increases energy consumption
It improves heat transfer
It lowers the condensation temperature
It has no effect

86

Stredne ťažká

How does correct condensation pressure control affect efficiency?


Maintains optimum operating conditions and reduces energy consumption
Causes leaks
It increases energy consumption
It has no effect

87

Stredne ťažká

How do condenser leaks affect energy efficiency?


They improve efficiency
Have no effect
Causes refrigerant loss and a drop in efficiency
They lower the temperature

88

Stredne ťažká

How important is the correct positioning of an air-cooled condenser?


It doesn’t matter
It should be installed in a well-ventilated area with unobstructed airflow
It should be housed in a small room
It should be close to heat sources

89

Stredne ťažká

How does hot air recirculation affect the condenser?


Impairs cooling and increases energy consumption
It reduces the pressure
It improves efficiency
It has no effect

90

Stredne ťažká

How does the insulation of central heating and domestic hot water pipework affect the operation of the heat pump’s condenser?


It increases the pressure
Reduces energy losses and improves the efficiency of the entire system
It doesn’t matter
It impairs cooling

91

Stredne ťažká

Which measure most improves the energy efficiency of the evaporator?


Increasing the amount of refrigerant
Restricted airflow
Increasing the condensation temperature
Regular defrosting of the evaporator

92

Stredne ťažká

How does evaporator icing affect the system’s operation?


Impairs heat exchange and increases energy consumption
It lowers the condensation temperature
It improves cooling performance
It has no effect

93

Stredne ťažká

How does dirt on the evaporator surface affect its performance?


It has no effect
Impairs heat exchange and increases energy consumption
It improves efficiency
It reduces the pressure

94

Stredne ťažká

What maintenance task is crucial for the evaporator?


Increasing the refrigerant charge
Lack of maintenance
Regular cleaning and defrosting
Reduced airflow

95

Stredne ťažká

What does an F-gas personal certificate (Category A2) authorise?


to make permanent joints by brazing in systems containing fluorinated greenhouse gases.
To recover refrigerant from equipment containing less than 3 kg of fluorinated greenhouse gases, or less than 6 kg in the case of hermetically sealed systems.
to repair, maintain or service refrigeration equipment and systems containing controlled substances.
for the purchase of lubricants and refrigeration oils, and for the testing of safety valves.

96

Stredne ťažká

How does superheating of the refrigerant at the evaporator outlet affect efficiency?


It only causes a drop in temperature
It has no effect
Excessive superheat reduces energy efficiency
It always improves performance

97

Stredne ťažká

How do leaks in the evaporator affect efficiency?


Have no effect
Improves performance
Increase capacity
These cause refrigerant loss and a drop in efficiency

98

Stredne ťažká

How important is correct expansion valve adjustment?


Causes leaks
It increases energy consumption
Ensures optimal evaporator charge and improves efficiency
It doesn’t matter

99

Stredne ťažká

How does inadequate insulation of the heat transfer circuit pipes affect evaporator performance?


It lowers the condensation temperature
Causes cooling losses and increased energy consumption
It improves efficiency
It has no effect

100

Stredne ťažká

How does correct TEV valve adjustment affect the system’s energy efficiency?


Ensures optimum superheat and improves system efficiency
It has no effect
Causes leaks
It increases energy consumption

101

Stredne ťažká

What happens if the superheat set by the TEV is too high?


It has no effect
The refrigerant charge will increase
Cooling efficiency will improve
Efficiency will drop because the evaporator is not being fully utilised

102

Stredne ťažká

How does a low superheat setting on the TEV affect performance?


It has no effect
It may lead to improved efficiency, but it increases the risk of the compressor becoming flooded with liquid
It increases operational safety
It reduces refrigerant flow

103

Stredne ťažká

How do contaminants in the system affect the operation of the TEV?


They lower the temperature
Have no effect
They improve its performance
They can cause it to become blocked and reduce efficiency

104

Stredne ťažká

What role does the filter-drier play in terms of system efficiency?


It increases the amount of refrigerant
It lowers the temperature
It doesn’t matter
Removes moisture and contaminants, improving the system’s efficiency

105

Stredne ťažká

How does proper insulation of components (e.g. pipes near the TEV) affect the system?


Prevents unwanted heat gains and improves efficiency
It increases energy consumption
It causes leaks
It doesn’t matter

106

Stredne ťažká

What does Regulation (EU) No 2024/573 of the European Parliament and of the Council cover?


The Regulation sets out health and safety requirements for soldering work.
The Regulation concerns gases that contribute to the greenhouse effect.
The Regulation concerns leak testing of stationary refrigeration, air-conditioning and heat pump equipment containing fluorinated greenhouse gases. The Regulation sets out the requirements relating to leak testing of such equipment.
The Regulation sets out requirements relating to brazing of refrigeration systems.

107

Stredne ťažká

How important is it to check the operation of the condensing pressure control valve in the system?


Ensures operation within the optimum pressure range and reduces energy losses
It causes a significant rise in temperature
It has no effect
It increases energy consumption

108

Stredne ťažká

How does the correct selection of a TEV affect energy efficiency?


It lowers the temperature
Ensures the system is matched to its capacity and operates optimally
It increases the amount of refrigerant
It doesn’t matter

109

Stredne ťažká

What is the main design difference in hydrocarbon-based refrigeration systems?


The need for explosion-proof measures due to the flammability of the refrigerant
Higher operating pressures
No need for safety measures
Lower energy efficiency

110

Stredne ťažká

What differences are there in the compressors used in hydrocarbon systems?


No differences
They do not require lubrication
They must be designed to operate with flammable refrigerants (e.g. hermetic compressors)
They must operate at higher pressures

111

Stredne ťažká

How can one check whether the system has been overcharged with refrigerant?


The compressor will operate under a lower load and the suction pressure will decrease
This cannot be checked with sufficient reliability, as the sight glass is not designed for this purpose.
Under normal conditions, there is a marked increase in condensing pressure because an excessive amount of refrigerant accumulates in the condenser, reducing the heat exchange surface area within it.
The refrigeration system is overcharged with refrigerant whilst in operation, and even under a very small heat load, frost forms on the suction side of the compressor

112

Stredne ťažká

Before charging the refrigeration unit with refrigerant, it is essential to…


carry out a leak test.
carry out a start-up test.
complete the unit’s data sheet.
check the compressor’s suction and discharge connections.

113

Stredne ťažká

What information must appear on the unit’s label?


The manufacturer’s logo and the weight of the unit.
Among other things: information stating that the unit contains a fluorinated greenhouse gas, together with the industrial designation of the gas or its chemical name, the mass of the gas and its CO₂ equivalent
Markings regarding the weight and capacity of the pipework, together with the colour code and chemical composition of the paints used to coat the frame and casing.
It does not matter what should be included on the device label.

114

Stredne ťažká

What is the base unit of temperature according to the International System of Units (Système International d’Unités)?


K
°F
°C
°R

115

Stredne ťažká

Which of the following are the most important pieces of information that should be included in the unit’s data sheet:


The make and model of the unit, so that the manufacturer can be contacted to obtain the technical information necessary for servicing.
Operator details, unit details, type and quantity of refrigerant, information regarding servicing and repairs.
Information regarding refrigerant recovery and unit dismantling.
The owner, installer and service technician of the unit.

116

Stredne ťažká

Who is responsible for drawing up the equipment or installation record?


There is no such obligation.
The equipment maintenance technician.
The person responsible for risk assessment.
The operator of the unit or system.

117

Stredne ťažká

Oil traps on the suction pipework are required:


always before any rise in the pipeline.
at the inlet to each component of the refrigeration system.
before the safety valve.
before the compressor.

118

Stredne ťažká

When is there a refrigerant leak, even though the compressor is still running?


When the suction pressure is low, superheat is high, subcooling is negligible and the temperature difference between the condenser and the expansion valve is small.
When we observe a rise in the refrigerant level in the liquid receiver and the subcooling increases.
When the sight glass is full of liquid refrigerant and we observe a rise in the oil level in the compressor sump.
When the condensing pressure and suction pressure rise, but there is no superheat.

119

Stredne ťažká

Which components of a refrigeration system can be classified as potential leak points (leaks) subject to regular leak tests?


Parts of the system located on the high-pressure side (from the compressor up to and including the expansion valve).
Hermetic compressors, liquid refrigerant tanks and liquid separators.
Fittings, valves including their stems, seals – including those in replaceable filters and dryers, components exposed to vibration, and connections to measuring, control and safety devices.
All parts of the refrigeration unit that are connected to the suction side of the refrigeration system.

120

Stredne ťažká

What is the test pressure during the pressure leak test of the unit?


The test pressure for leak testing is equivalent to the maximum operating pressure measured during the operation of the refrigeration unit.
The test pressure is determined by the person carrying out the leak test based on their experience.
The test pressure (maximum) is 30 bar.
According to the PN-EN 378 standard, at least 0.25 times the maximum permissible pressure for the system (PS).

121

Stredne ťažká

In which part of the refrigeration unit must the recommended leak test be carried out?


The check must be carried out on all parts of the refrigeration system that are connected to the discharge side of the refrigeration circuit.
The test must be carried out at all points on the refrigeration unit where there is a potential risk of refrigerant leakage.
The check should only be carried out at the connection points for measuring instruments (pressure switches, pressure gauges, temperature sensors).
The test must be carried out on the compressor shut-off valves, solenoid valves and filters.

122

Stredne ťažká

When can a given unit be considered perfectly leak-tight?


A device can be considered perfectly leak-tight if gas bubbles appear when it is submerged in water.
The device in question is perfectly leak-tight when we have carried out a check using a permanently installed electronic detector.
A given device can be considered perfectly leak-tight when the pressure drop during the test does not exceed 0.1 bar.
A given unit can be considered perfectly leak-tight if, during a leak test, the pressure remains constant, taking into account pressure changes caused by temperature variations. Any drop in pressure indicates a leak and requires the location of the leak to be identified.

123

Stredne ťažká

What does EU Regulation 1516/2007 cover?


The Regulation sets out requirements relating to brazing of refrigeration systems.
The Regulation sets out health and safety requirements for soldering work.
The Regulation addresses the disposal of gases that contribute to the greenhouse effect.
The Regulation concerns leak testing of stationary refrigeration, air-conditioning and heat pump equipment containing fluorinated greenhouse gases. The Regulation sets out the requirements for leak testing of such equipment.

124

Stredne ťažká

How should the pressure be increased during a pressure leak test?


We increase the pressure gradually whilst checking for leaks, until the test pressure is reached, at a rate of no more than 2 bar/min
We increase the pressure at a rate of 10 bar/s.
We increase the pressure in any way.
We increase the pressure as quickly as possible.

125

Stredne ťažká

What electronic equipment should be used to carry out leak testing?


Only with devices fitted with an ‘Ion Pump’ sensor.
Only with devices fitted with hot cathodes.
Only with devices fitted with an infrared detector.
Only using devices with verified measurement sensitivity.

126

Stredne ťažká

What documentation should be checked before starting a leak test?


Check the stock ledger (accounts).
Check the time sheets of the staff responsible for the machinery/equipment.
Check the operating instructions for the machine/equipment.
The maintenance log and the machine/device operating instructions must be checked.

127

Stredne ťažká

What information must be recorded when drawing up the leak test report?


The date of the inspection, the number of faults (leaks), the location of the faults (leaks), the proposed method of rectifying the fault/defect (leak), attached documents and a signature.
The date of the inspection, a record of the occurrence of the leak, and a signature.
The method used to carry out the leak test, the number of faults, the method of repairing the faults, the time taken to work on the installation, and the cost of the repair.
The number of locations where leaks have occurred and the date of the inspection.

128

Stredne ťažká

What pressure values should be used for the pressure leak test?


The pressure for the leak test is 2–3 bar.
At the discretion of the person authorised to carry out the pressure test.
Use a pressure not exceeding the maximum permissible pressure for the system (PS).
The pressure value for the leak test is 10–12 bar.

129

Stredne ťažká

What is temperature slip?


It involves a decrease in temperature.
A specific temperature corresponds to a given vapour pressure.
A specific temperature cannot be assigned to a given vapour pressure. There is a temperature difference between the start and end of evaporation.
It involves an increase in temperature.

130

Stredne ťažká

In which appliances and systems is the installation of a permanent leak detection system required?


In equipment and installations containing at least 30 kg of fluorinated greenhouse gases.
In equipment and systems containing at least 50 tonnes of CO₂ equivalent.
In equipment and systems containing at least 5 tonnes of CO₂ equivalent.
In equipment and systems containing at least 500 tonnes of CO₂ equivalent.

131

Stredne ťažká

Which category of F-gas certificate (A1, A2, B, C, D, E) authorises the performance of leak tests on refrigeration equipment:


All except category D.
Only categories A1 and A2.
Categories D and E.
Category E only.

132

Stredne ťažká

Why is it advisable to subcool the liquid refrigerant?


This is advisable because it allows a smaller expansion valve to be used (less superheat at the valve).
This is advisable because it ensures that the liquid refrigerant, free of vapour bubbles, enters the expansion valve.
This is advisable because it allows a smaller condenser to be used (smaller heat exchange surface area).
This is advisable because it allows a smaller evaporator to be used (lower refrigerant temperature at the evaporator inlet).

133

Stredne ťažká

What should be done following repairs to a leak in the refrigeration unit of a refrigerated trailer?


You must enter the details into the equipment log (including the quantities of refrigerant recovered and used) and inform the Operator that an additional leak test must be carried out by a certified person within one month of the repair.
An invoice for the service work carried out must be issued as soon as possible.
A visual inspection should be carried out only on bolted and soldered joints.
The unit must be charged with an alternative refrigerant, started up, and the refrigerant parameters checked at the service valve located on the liquid receiver.

134

Stredne ťažká

Recovery of fluorinated greenhouse gases means:


The collection and storage of fluorinated greenhouse gases originating, for example, from machinery, equipment and containers.
The final decommissioning and withdrawal from service or use of a product or piece of equipment containing fluorinated greenhouse gases.
The reprocessing of fluorinated greenhouse gases to achieve their specified standard properties.
The reuse of fluorinated greenhouse gases following a basic purification process.

135

Stredne ťažká

Who is authorised to recover refrigerant from stationary refrigeration equipment:


The administrator of the operator’s account.
The operator.
The owner of the installation.
A service technician holding an F-gas certificate in the relevant category.

136

Stredne ťažká

Recovered refrigerants must be stored:


In any used refrigerant cylinder.
In any pressure vessel that has been officially certified.
In a specially adapted and labelled cylinder fitted with a two-way valve.
In a cylinder that previously contained the same type of refrigerant.

137

Stredne ťažká

When should the recovery of fluorinated greenhouse gases be carried out:


Only prior to the final disposal of equipment.
Always during servicing and maintenance of equipment.
Before each leak test of the equipment.
Before the final disposal of equipment and, where applicable, during its servicing and maintenance.

138

Stredne ťažká

What should be done if the refrigerant recovered from the system is contaminated, e.g. with acid, air or moisture?


Purify the mixture by passing it through a particulate filter and reuse it.
Such a mixture must be handed over to a specialist authorised company for regeneration or disposal.
You should attempt to purify the mixture yourself using a dehydrating filter.
Add a special contaminant neutraliser to the mixture.

139

Stredne ťažká

What should be done if different types of refrigerants become mixed in a storage cylinder (container)?


You should attempt to separate the mixture into its individual components.
Add a special refrigerant to the mixture.
Send this mixture to a specialist authorised company to have it neutralised.
The mixture should be purified by passing it through a filter-drain and reused.

140

Stredne ťažká

How does refrigerant recovery using the Push-Pull method work?


This involves the refrigerant being alternately drawn from the suction side and then from the discharge side of the refrigeration unit (compressor).
This involves injecting nitrogen from the cylinder into the unit and expelling the liquid refrigerant from the unit.
This involves using a suction device (compressor) to ensure that the refrigerant, in liquid form, is transferred into the cylinder.
It involves using a recovery unit to draw (pull) the refrigerant vapour from the cylinder and then force it (push) into the low-pressure side of the system.

141

Stredne ťažká

What are the methods for managing waste refrigerant?


Recycling, regeneration, disposal.
Recovery, disposal.
Disposal, storage.
Regeneration, recovery.

142

Stredne ťažká

The most advantageous method of managing waste refrigerant is:


Regeneration.
Disposal.
Recycling.
Storage.

143

Stredne ťažká

The lower the evaporation temperature, ...


...the lower the refrigerant density, and the greater the cooling capacity of the compressor.
...the lower the density of the refrigerant and the lower the mass of the flowing refrigerant.
...the greater the density of the refrigerant and the mass flow rate of the flowing refrigerant.
…the greater the density of the refrigerant and the lower the mass flow rate of the refrigerant.

144

Stredne ťažká

How should pressure vessels (e.g. refrigerant cylinders) be marked?


They should bear the manufacturer’s logo and the date of manufacture.
They should bear, amongst other things, information such as: the number of the standard applied to their design, construction and testing; the identification marks of the country of approval and the inspection body; the date of the acceptance test; and the manufacturer’s and operational marks.
They should bear only markings relating to weight and capacity.
It is irrelevant how pressure vessels should be marked.

145

Stredne ťažká

The recovery of refrigerants does not require the use of:


An electronic leak detector.
A refrigerant recovery station.
Hoses with shut-off valves.
Scales with a measurement range suitable for the size of the cylinder being filled.

146

Stredne ťažká

What functions does the compressor perform in a refrigeration system?


The compressor condenses the refrigerant.
The compressor draws in refrigerant vapour from the evaporator, compresses it, and then forces it into the condenser, raising the pressure to the required condensing pressure.
The compressor compresses ambient air and increases the pressure of the refrigerant.
The compressor creates a vacuum on the suction side of the system

147

Stredne ťažká

What is compressor flooding?


A large amount of liquid refrigerant in the evaporator.
Flooding of the compressor due to rainfall.
Suction of liquid refrigerant into the compressor’s suction line.
Flooding the compression chamber with liquid refrigerant or oil.

148

Stredne ťažká

To what extent do we regulate the compressor motor’s rotational speed when using a frequency converter?


Up to a maximum of 10 per cent.
Approximately from 30 to 75 Hz, which corresponds to around 60% to 150% of the cooling capacity.
From approximately 30% to 90% of capacity.
Regulating the compressor motor speed is not the same as regulating the cooling capacity.

149

Stredne ťažká

Why is it essential to observe the correct phase sequence for scroll compressors and screw compressors?


Because this type of compressor has difficulty starting up if the phase sequence is changed.
Because these types of compressors are sensitive to voltage drops.
Because changing the phase sequence would reverse the direction of rotation of the compressor rotors, which could result in damage to the compressors.
Because the motor speed would decrease, and consequently the compressor’s capacity.

150

Stredne ťažká

The cycle of a two-stage vapour-compression refrigeration system should have, in each stage of the system:


a compression ratio of less than 8.
a compression ratio of less than 6
a compression ratio of less than 18.
a compression ratio greater than 8.

151

Stredne ťažká

Why is it necessary to seal the shafts in gland-sealed refrigeration compressors?


Because it prevents oil leakage.
Because it protects the compressor’s crankshaft bearing.
Because it ensures the bearing remains lubricated.
Because we need to prevent air from entering the compressor and we need to prevent refrigerant from leaking from the compressor.

152

Stredne ťažká

When is the refrigerant sufficiently cooled?


When the evaporator is covered in frost.
When the outlet from the condenser is cold.
When the liquid distributors are warm.
When no vapour bubbles are observed forming in the liquid sight glass.

153

Stredne ťažká

Why should the compressor crankcase be heated?


Heating prevents the refrigerant from dissolving in the oil.
Heating keeps the lubricating oil in a liquid state.
Heating ensures that the lubricating oil is de-watered.
Heating improves the dissolution of the refrigerant in the oil, which is beneficial for its viscosity.

154

Stredne ťažká

What are compressor sets?


These are multiple (several) air-cooled condensers.
These are units consisting of two-stage compressors.
These consist of a larger number (several) of compressors connected in parallel and mounted on a common frame.
These are sets comprising several compressors connected in any configuration.

155

Stredne ťažká

What are the advantages of compressor units?


Space-saving and lower energy consumption.
These are inexpensive and easy-to-install units.
The ability to adjust the cooling capacity as required.
Easy modification of the system.

156

Stredne ťažká

What do we mean by the ‘application range’ of a compressor?


By this term, we mean that the compressor’s application range is determined by the evaporation temperature ‘to’ at a given ambient temperature.
By this term, we mean the following parameters: compressor capacity, type of refrigerant, and the compressor’s geometric dimensions.
By this term, we mean that the compressor’s operating range is determined by the evaporation temperature ‘to’ during operation.
By this term, we mean the following parameters: the evaporation and condensation temperatures (to and tk), or the pressure values that determine the compressor’s application.

157

Stredne ťažká

What are the basic functions of oil in a compressor?


The oil lubricates both the bearings and the sliding surfaces of the compressor components, and cools the compressor by transferring the heat generated during compression to the compressor’s outer casing.
The oil absorbs moisture from the refrigerant that enters the compressor.
The oil seals the gap between the piston and the cylinder.
The oil seals any leaks that develop in the system.

158

Stredne ťažká

What are the most effective ways of regulating the compressor’s cooling capacity?


Using an expansion valve.
By changing the compressor’s displacement, by varying the rotational speed, or by deactivating individual cylinders.
By partially covering the evaporator to reduce the heat exchange surface area.
By means of pressure control valves.

159

Stredne ťažká

What does compressor bypass control involve?


High-pressure liquid refrigerant is injected on the suction side of the compressor.
Hot, high-pressure refrigerant vapour is drawn in on the suction side of the compressor.
Refrigerant in the form of cooled, high-pressure vapour is introduced into the suction line.
The bypass control is not used to regulate the compressor.

160

Stredne ťažká

What is the fundamental difference between hermetic and semi-hermetic compressors?


Both types of compressors are disassemblable, and the difference lies in their varying capacities.
The housing of a hermetic compressor and the compressor itself form a single unit.
The casing of semi-hermetic compressors can be dismantled, whereas the casing of hermetic compressors cannot be dismantled.
Semi-hermetic compressors are characterised by the quiet operation of the entire unit.

161

Stredne ťažká

How does a scroll compressor work?


A scroll compressor is also known as a turbo compressor.
It uses two screws to compress the refrigerant.
It is a type of piston-type device.
It is a device fitted with two spirals. It is a type of positive displacement (volumetric) compressor in which compression takes place through the interaction of the two spirals.

162

Stredne ťažká

What physical process takes place in the evaporator?


It cools the refrigerant flowing through it.
The medium flowing through the evaporator (glycol, water) evaporates, whilst the refrigerant condenses.
It causes the refrigerant flowing through it to condense.
The liquid refrigerant evaporates and a small amount of it becomes superheated.

163

Stredne ťažká

What is the purpose of regulating the compressor’s capacity?


It ensures adequate lubrication of the compressor.
It allows the cooling capacity to be adjusted to meet requirements.
It ensures that the cooling capacity is adjusted based on condensing temperatures.
Capacity control protects the compressor from low thermal loads.

164

Stredne ťažká

Why is inverter speed control suitable for refrigeration compressors?


Inverter speed control reduces energy consumption only under natural conditions.
By reducing the speed of the refrigeration compressor motor, inverter speed control improves the return oil flow to the compressor.
Inverter speed control enables continuous, smooth regulation of cooling capacity.
Inverter speed control can be used with any type of compressor to ensure adequate lubrication.

165

Stredne ťažká

Does the suction gas temperature affect the cooling capacity of the compressor?


It does, but only if the gas is deeply cooled.
Temperature has no effect on the compressor’s cooling capacity.
It has a significant effect on performance.
It does, but only for reciprocating compressors.

166

Stredne ťažká

In the case of compressor units fitted with an oil level control system, is it necessary to install the compressors at the same height?


Only screw compressors.
Only scroll compressors.
Yes.
No.

167

Stredne ťažká

What functions does a compressor powered by the vehicle’s engine perform in a transport refrigeration system?


The compressor compresses ambient air and increases the pressure of the refrigerant.
This compressor draws in refrigerant vapour from the evaporator, compresses it and then forces it into the condenser whilst the vehicle’s engine is running.
This compressor creates a vacuum on the suction side of the system whilst the vehicle’s engine is switched off.
This compressor condenses the refrigerant whilst the vehicle is in motion.

168

Stredne ťažká

Which natural fluids absorb heat from the refrigerant in the condenser?


Water or air.
Water and an antifreeze mixture.
Ammonia
Air and CO2.

169

Stredne ťažká

What is the function of the condenser in refrigeration systems?


The heat absorbed in the evaporator is then released into the environment via the condenser
Heat from the compressor is then released into the environment via the condenser.
The heat absorbed in the evaporator and transferred during the compression process is then released into the environment via the condenser.
Heat released in the regenerative heat exchanger is absorbed by the condenser.

170

Stredne ťažká

If the condensation temperature is higher than the critical point temperature of the refrigerant, condensation:


temperature has no effect on condensation.
will not occur.
will occur provided a specially designed condenser is used.
will always occur regardless of the temperature.

171

Stredne ťažká

How does the subcooling of the refrigerant take place within a refrigeration system?


Subcooling using high-pressure hot vapour.
Subcooling using an additional heat exchanger and liquid nitrogen.
Subcooling of the liquid refrigerant in the final section of the condenser.
Subcooling of the refrigerant using oil (dissolving the refrigerant in oil).

172

Stredne ťažká

What is the purpose of controlling the condenser fan speed?


Condenser fan speed control reduces energy efficiency.
Condenser fan speed control ensures that the condensing pressure is maintained at the correct level.
Dispersion of the refrigerant in the event of a system leak.
Condenser fan speed control safeguards against the maximum permissible condensing pressure.