1

Ťažká

What is the main difference between a dry evaporator and a flooded evaporator?


A dry evaporator allows the entire refrigerant to evaporate in the pipe upstream of the compressor; in a flooded evaporator, part of the refrigerant remains in a liquid state within the evaporator
A dry evaporator has a lower operating pressure than a flooded one
A dry evaporator is filled with refrigerant liquid, whilst a flooded evaporator is filled with gas
A dry evaporator does not require an expansion valve, whereas a flooded one does

2

Ťažká

What is the typical pressure in deep-freezing systems (below −40 °C) for an evaporator in a system using R717?


A pressure varying between 10 and 20 bar
Negative pressure (vacuum), below 0 bar
Atmospheric pressure, approximately 1 bar
Positive pressure, in the range of 5–10 bar

3

Ťažká

Why are PFAS substances formed as a result of the decomposition of certain F-gases problematic?


They are readily biodegradable, so they only pollute the environment for a short time
They cause rapid cooling of the atmosphere
They are persistent, accumulate in the environment and may be toxic
They are climate-neutral

4

Ťažká

What is the basic requirement when charging a system with R717 (NH₃)?


Charging should take place in a well-ventilated area using appropriate personal protective equipment
NH₃ can be charged together with air
Charging must only take place at temperatures below 0°C
Charging can be carried out without personal protective equipment

5

Ťažká

How should oil be handled in systems using R717?


The oil should be checked regularly and any excess removed from the lower parts of the units to prevent reduced heat transfer and leaks
Oil has no effect on the system’s operation
Oil can be mixed with any refrigerant
The oil does not require any monitoring

6

Ťažká

What is the correct procedure for recovering R717 from a system?


The refrigerant must be recovered into suitable, leak-proof tanks designed for NH₃
The gas can be released into the atmosphere
The refrigerant can be drained into the sewer system
Recovery is not required

7

Ťažká

How should R717 (NH₃) be stored?


Near heat sources
In unmarked plastic containers
In sealed, labelled containers, in a cool and well-ventilated place
In any open containers

8

Ťažká

What should be done in the event of R717 contamination?


Add water to dilute it
Release into the atmosphere
The refrigerant must be purified or sent for disposal in accordance with regulations
Continue to use without restriction

9

Ťažká

What is the main hazard associated with an R717 leak during maintenance work?


Toxic to humans and may cause chemical burns
Damage to electrical equipment only
Increased cooling efficiency
No risk whatsoever

10

Ťažká

What action should be taken if an NH₃ leak is detected?


Evacuate personnel immediately and remove the source of the leak, if it is safe to do so
Close your eyes and carry on working
Ignore it and carry on working
Increase the pressure in the system

11

Ťažká

What role do scrubbers play in NH₃ systems?


They are used to measure temperature
Neutralises ammonia through absorption in a liquid (e.g. water)
They store the refrigerant
They increase the pressure in the system

12

Ťažká

How should the system be prepared before filling with R717?


Check for leaks, remove air and moisture, and create a vacuum
Simply start it up
The pressure must be increased above the standard level
There is no need to check it

13

Ťažká

What are the transport requirements for R717?


It can be transported without labelling
Must be transported in suitable, labelled containers in accordance with ADR regulations
It can be transported in open containers
Transport is not subject to regulations

14

Ťažká

What personal protective equipment is required when working with NH₃?


Workwear only
Safety goggles, gloves and respiratory protective equipment
Only a safety helmet
No requirements

15

Ťažká

Which statement best describes the behaviour of R717 and mineral compressor oil?


In an R717 system, a return oil line cannot be used because the oil is too hot
R717 does not mix with compressor oil, so the oil remains in the system on the high-pressure side as a layer above the R717
R717 does not mix with compressor oil, so the oil remains in the system on the low-pressure side as a layer beneath the R717
R717 mixes very well with compressor oil and easily returns to the compressor

16

Ťažká

Which system may require manual oil recovery?


Supercritical ‘booster’ system using R744
Secondary system using R744
R744 cascade system
An R717 system

17

Ťažká

Which refrigerant is lighter than air?


R744
R1270
R1234ze
R717

18

Ťažká

R717 is highly corrosive to


copper
stainless steel
aluminium
titanium

19

Ťažká

What is the effect of repeatedly opening the relief valve?


The valve remains fully open continuously
The relief pressure rises
The relief pressure drops
The valve will not open

20

Ťažká

What is the relationship between the pressure (P) and temperature (T) of nitrogen at the start (1) and end (2) of the leak test?


P2 = T2/(P1 × T1)
P2 = (P1 × T1)/T2
P2 = T1/(P1 × T2)
P2 = (P1 × T2)/T1

21

Ťažká

What is the recommended alarm level for fixed leak detection systems for R717?


5,000 ppm
500 ppm
50,000 ppm
500,000 ppm

22

Ťažká

Why are compressors with a separate electric motor most commonly used in R717 (NH₃) refrigeration systems?


Because compressors with a separate motor are cheaper
Because NH₃ reacts with the motor windings and hermetic compressors are not used
To increase the amount of refrigerant in the system
To reduce the condensing pressure

23

Ťažká

Which type of compressor is most commonly used in large ammonia systems?


Hermetic scroll
A reciprocating or screw compressor
Rotary vane compressor
Diaphragm compressor

24

Ťažká

How is the capacity of a piston compressor regulated in NH₃ systems?


Solely by adjusting the oil volume
By reducing the refrigerant charge
By unloading the cylinders or changing the rotational speed
By increasing the condensing pressure

25

Ťažká

How is the capacity of a screw compressor most commonly controlled?


By changing the type of oil
By closing the suction valve
By adjusting the oil level
By using a slide valve

26

Ťažká

When is two-stage compression used in NH₃ systems?


Only with water-cooled condensers
At very low vapour pressures and high pressure differentials
At small temperature differences
Exclusively in small systems

27

Ťažká

What is the advantage of two-stage compression over single-stage compression?


No need for a separator
Higher energy consumption
Higher efficiency and lower discharge temperature
Lower efficiency

28

Ťažká

How does an evaporative condenser used in NH₃ systems work?


It does not require a water supply
It transfers heat only to the air
It utilises the evaporation of water to increase cooling efficiency
Operates without a fan

29

Ťažká

What is the function of the liquid separator in an NH₃ system?


It prevents liquid from entering the compressor
Regulates the condensing pressure
Increases the discharge temperature
It separates oil from the refrigerant

30

Ťažká

What is the purpose of monitoring the liquid level in the separator?


To maintain the correct refrigerant level and prevent the compressor from flooding
To reduce the condensing temperature
To control the condenser fan
To increase the oil volume

31

Ťažká

What is the role of the float switch in NH₃ systems?


It is used to detect leaks
It monitors the liquid level in the tank or separator
It controls the fan’s operation
It regulates the condensation temperature

32

Ťažká

What is a thermosiphon in NH₃ systems?


A type of evaporator
A defrosting device
A type of safety valve
An oil circulation system utilising differences in pressure and temperature

33

Ťažká

Why are oils that are immiscible with the refrigerant used in NH₃ systems?


To reduce the pressure
Because the oil mixes only with water
Because NH₃ does not mix with most compressor oils
To increase the amount of refrigerant

34

Ťažká

What is the main function of an oil separator in NH₃ systems?


To separate the oil from the refrigerant and return the oil to the compressor
To increase fan efficiency
To lower the condensation temperature
Removing moisture from the system

35

Ťažká

Which NH₃ system features direct evaporation of the refrigerant in the evaporator?


Thermosiphon system
Indirect system
Glycol system
Direct expansion (DX) system

36

Ťažká

What is the characteristic feature of a flooded evaporator system?


The evaporator contains a large amount of liquid, which improves heat transfer
No level control is required
No separator is used
The evaporator is filled exclusively with vapour

37

Ťažká

What is the main difference between a direct and an indirect system?


In an indirect system, no compressor is used
In a direct system, there is no evaporator
In an indirect system, NH₃ cools an intermediate medium (e.g. glycol), which in turn cools the load
In an indirect system, NH₃ flows directly into the space being cooled