1

Difficult

Why do CO₂ refrigeration systems require special attention when separating liquid and oil?


CO₂ is flammable, so separators cannot be used
CO₂ does not require lubrication, so separators are unnecessary
CO₂ operates at high pressure, which increases the risk of compressor failure and leaks
CO₂ cannot be used in systems with sight glasses

2

Difficult

What is the critical pressure of CO₂ (R744)?


Approximately 31 bar
Approximately 74 bar
Approximately 10 bar
Approximately 120 bar

3

Difficult

What characterises the transcritical process in CO₂ systems?


It is irrelevant to the operation of the system
The system operates above the critical point and the refrigerant does not condense in the conventional manner
Conventional condensation occurs
It occurs only at low temperatures

4

Difficult

What characterises the subcritical CO₂ process?


The absence of condensation
Operation above the critical point
The absence of evaporation
The conventional condensation process below the critical point

5

Difficult

What is the log(p)-h diagram for CO₂ used for?


To regulate pressure
To measure temperature
To detect leaks
For analysing thermodynamic processes in a refrigeration system

6

Difficult

What can be read from the log(p)-h graph?


Only the temperature
Only the amount of refrigerant
Pressure, enthalpy, temperature and state of the refrigerant
Only the humidity

7

Difficult

What are CO₂ saturation tables used for?


To regulate the compressor
To measure humidity
To determine the oil quantity
To determine the relationship between temperature and pressure at saturation

8

Difficult

What does the CO₂ saturation state mean?


Dry ice state
Equilibrium between the liquid and vapour phases
A state in which the refrigerant is only a gas
A state of high pressure

9

Difficult

When can dry ice (solid CO₂) form?


At high temperature
At high pressure
During normal operation of the system
In the event of a sudden drop in pressure and temperature below the triple point

10

Difficult

What risks are associated with the formation of dry ice in a CO₂ system?


Blocked pipes and system damage
Pressure reduction
No risk
Improved efficiency

11

Difficult

How does the CO₂ pressure change as the temperature rises?


It first decreases, then increases
It decreases
Rises sharply
It remains the same

12

Difficult

Why is understanding the log(p)-h graph particularly important for CO₂?


As CO₂ systems operate in different modes (sub- and transcritical) and require detailed analysis
It is only used for design purposes
It only applies to NH₃
It doesn’t matter

13

Difficult

What happens to CO₂ above the critical point?


It turns into a solid
It ceases to conduct heat
It turns into a liquid
It transitions to a supercritical state (no distinction between liquid and gas)

14

Difficult

Why do CO₂ systems require precise pressure control?


Due to low pressures
Because there are no valves
They do not require control
Due to significant pressure changes with temperature fluctuations

15

Difficult

What is the main characteristic of R744 (CO₂) refrigeration systems?


Very high operating pressures
Low operating pressures
Low energy efficiency
No need for regulation

16

Difficult

What are the requirements for piping materials in CO₂ systems?


They may be made of any material
They must be made exclusively from plastics
It does not matter
They must be able to withstand high pressures (e.g. high-grade steel)

17

Difficult

How does a booster system work in CO₂ installations?


It reduces the amount of refrigerant
It is used to store the refrigerant
It reduces the pressure in the evaporator
It utilises two stages of compression (low and medium pressure) in a single system

18

Difficult

What is the function of high-pressure control valves in CO₂ systems?


They regulate oil flow
They control the pressure on the high-pressure side and optimise system operation
They are used to store the refrigerant
They lower the evaporator temperature

19

Difficult

Why is pressure optimisation in CO₂ systems crucial?


It reduces the ambient temperature
It enables the system to achieve maximum energy efficiency
It reduces the amount of refrigerant
It doesn’t matter

20

Difficult

What role do parallel-operating compressors play in CO₂ systems?


They lower the ambient temperature
They increase energy consumption
It does not matter
They enable gas recovery from the medium-pressure stage and improve efficiency

21

Difficult

How does an ejector work in a CO₂ system?


It increases the amount of refrigerant
It uses the energy of the higher-pressure refrigerant to raise the pressure of the refrigerant from the lower stage, which improves efficiency
Stores the refrigerant
It lowers the evaporator temperature

22

Difficult

What is the function of liquid ejectors in CO₂ systems?


They reduce atmospheric pressure
They increase the amount of oil
They raise the refrigerant temperature
They assist with liquid recovery and improve evaporator feed

23

Difficult

What are the characteristics of partially flooded systems in CO₂ systems?


Low operating pressure
Lack of regulation
The presence of liquid in the evaporator, which improves heat transfer and efficiency
The absence of liquid in the evaporator

24

Difficult

What is the main risk associated with static pressure in CO₂ systems?


Increased efficiency
A drop in temperature
A decrease in refrigerant quantity
A rise in pressure resulting from the refrigerant heating up whilst at rest

25

Difficult

How can standstill pressure in CO₂ systems be reduced?


By increasing the refrigerant charge
By shutting down the system completely
By using parallel compressors and external cooling systems
By increasing the temperature

26

Difficult

What does ‘stagnation’ of a refrigeration system mean in the context of CO₂?


Normal system operation
A drop in temperature
Improved efficiency
A lack of refrigerant flow, which can lead to increased pressure and safety risks

27

Difficult

Why do CO₂ systems require more advanced automation than traditional systems?


Due to the need for precise control of pressure and temperature
Because there are no valves
They do not require automation
Due to low pressures

28

Difficult

Which safety class applies to R744?


A3
B2L
A1
A2

29

Difficult

In an R744 system operating in supercritical mode, the refrigerant entering the evaporator expansion valve is...


A supercritical fluid
A two-phase mixture at intermediate pressure
A subcooled liquid
Saturated vapour at intermediate pressure

30

Difficult

In R744 supercritical systems, the gas cooler outlet valve controls:


The pressure in the gas cooler
The outlet temperature of the gas cooler
The gas cooler fans
The inlet temperature to the gas cooler

31

Difficult

What is the main reason for using K65 copper tubing in some R744 systems?


They bend easily
They can withstand higher pressures
They have good low-temperature performance
They come in a wider range of diameters

32

Difficult

Which of the following statements is correct regarding the installation of Schrader valves?


All Schrader valve cores are suitable for all refrigerants
Schrader valves must not be used in R744 systems
When brazing the valve body to the system, the core must be removed, then refitted and tightened to the correct torque
Hydrocarbons leak through Schrader valves

33

Difficult

Which refrigerant can be detected using phenolphthalein paper?


R744
R1270
R717
R1234ze

34

Difficult

How does a refrigerant shortage affect the high-pressure side of the system (without discharge pressure regulation)?


The discharge pressure will be lower, and the subcooling will be lower
Discharge pressure will be higher, and the degree of subcooling will be higher
Discharge pressure will be lower, subcooling will be higher
Discharge pressure will be higher, and the degree of subcooling will be lower

35

Difficult

What is the benefit of using helium as a tracer gas in nitrogen during a pressure test?


It has a distinct odour
It is non-flammable
It has smaller molecules and diffuses more easily
It has a higher pressure than pure nitrogen

36

Difficult

Why should an R744 system that has been drained be initially charged with the refrigerant in gaseous form?


To prevent the drain valve from opening
To prevent damage to the compressor
To ensure that R744 is charged slowly
To prevent the formation of dry ice

37

Difficult

If an R744 system contains moisture because it has not been properly drained, what is the likely consequence?


Reduced cooling capacity
Excessively high discharge pressure
The formation of hydrogen fluoride, which will decompose into hydrofluoric acid and damage the compressor
The formation of carbonic acid, which will cause damage to the system

38

Difficult

The pressure of R744 at a saturation temperature of 20 °C is approx.


25 bar g
56 bar g
14 bar g
90 bar g

39

Difficult

At an ambient temperature of 25°C, the standby pressure in the low-pressure stage of an R744 cascade system will typically be…


The same as the pressure set on the relief valve
The same as the high-pressure setting on the pressure switch
Higher than the maximum permissible pressure in the low-pressure stage
27.5 bar g

40

Difficult

What is the correct definition of critical temperature?


The temperature at which the vapour pressure of a liquid is equal to the ambient pressure surrounding the liquid
The temperature at which, for certain substances, electrical resistance is zero
The temperature above which there are no distinct liquid and gaseous phases
The temperature at which a substance changes from a gaseous to a solid state

41

Difficult

In a supercritical system, under supercritical conditions, the working fluid in the gas cooler


loses heat during a phase change
it loses heat when its pressure drops
loses heat at constant temperature and pressure
it loses heat as its temperature drops