1

Stredne ťažká

What is R1270?


n-Butane
Isobutane
Propane
Propene (propylene)

2

Stredne ťažká

What is the main design difference in hydrocarbon refrigeration systems?


Lower energy efficiency
No need for safety measures
Higher operating pressures
The need to eliminate ignition sources and limit the charge because of the refrigerant's flammability

3

Stredne ťažká

How do compressors used in hydrocarbon systems differ?


They must be approved by the manufacturer for the specific flammable refrigerant (e.g. electrical components that are not ignition sources, suitable oil)
There is no difference
They must operate at higher pressures than HFC compressors
They need no lubrication

4

Stredne ťažká

What distinguishes class 2L refrigerants from class 2?


Heat of combustion above 19 MJ/kg
Higher toxicity
No lower flammability limit
A maximum burning velocity of no more than 10 cm/s

5

Stredne ťažká

What is the lower flammability limit (LFL) of propane R290?


Approx. 0.307 kg/m³
Approx. 0.038 kg/m³ (approx. 2.1% by volume)
Approx. 1.8 kg/m³
Approx. 0.38 kg/m³

6

Stredne ťažká

Equipment marked 'Ex II 3G' may be used in zone:


1
0
20 (dusts)
2 (explosive gas atmosphere unlikely and short-lived)

7

Stredne ťažká

How is explosion hazard zone 2 defined?


An explosive atmosphere is present continuously or for long periods
An area where flammable refrigerants are never used
An explosive atmosphere is likely to occur in normal operation
An explosive atmosphere is not likely in normal operation and, if it occurs, persists only for a short period

8

Stredne ťažká

Under which UN number is propane (R290) carried under ADR?


UN 3337
UN 1978
UN 3252
UN 1005

9

Stredne ťažká

At what concentration should a portable flammable gas detector used for R290 work raise an alarm at the latest?


At 5% propane by volume
No higher than 25% of LFL
At 150% of LFL
At 100% of LFL

10

Stredne ťažká

How should a recovery cylinder be prepared before filling it with a hydrocarbon refrigerant?


Partly fill it with nitrogen to 5 bar
Evacuate it (no air) and label it for the specific flammable refrigerant
Purge it with compressed air
No preparation is needed

11

Stredne ťažká

What is the correct approach in a risk analysis before work on an HC system?


Having a fire extinguisher is sufficient
First select PPE, then possibly remove ignition sources
The risk analysis is done after the work is finished
First eliminate hazard sources (e.g. ignition sources); where this is not possible, identify them and apply mitigating measures (ventilation, detection, PPE)

12

Stredne ťažká

Why must the charge of small, critically charged R290 systems be weighed to within a few grams during service?


Because scales are not needed – charging is done by sight glass
Because extra R290 improves efficiency
Because R290 is more expensive than HFCs
Small charge deviations significantly change superheat/subcooling and efficiency, and overcharge increases the risk in a leak